www.hi-velocity.com
© 1995-2017 Energy Saving Products Ltd.
Some building codes call for the use of a secondary drain pan
underneath the entire unit (Fig. RPM-05). Any installation that has
the potential of property damage due to condensate must have a
secondary drain pan installed. If the unit is installed in a high heat
and/or high humidity location, extra insulation around the unit
casing may be required. This will prevent excessive condensate
from forming on the outer surface of the casing.
Secondary Drain Pan
Fig. RPM-05 - Secondary drain pan
Drain Connections
All RPM-E modules come with a ¾” (19mm) primary and
secondary outlet. The condensate drain must have a vented
p-trap installed (Fig. RPM-05), and run at a slope of ¼” (6.7mm)
per foot in the direction of the drain. When installing the P-trap,
one must be installed on both the primary and secondary outlets.
The P-traps must have a minimum depth of two inches (51mm).
Due to the high negative pressure of the blower system, the
RPM-E will hold some amount of water during operation. Once
this level has been achieved, condensate will flow from the coil
regularly. When the unit shuts down, or lowers speed, the force
is released, allowing the held condensate to empty from the
drain pan. During this time, condensate may flow from both the
primary AND secondary drains.
Locate the outdoor unit in a suitable location, as close as
possible to the fan coil. Maintain the clearances recommended by
the manufacturers of the outdoor unit, to ensure proper airflow.
The outdoor unit must be installed level, in a properly supported
location. A liquid line filter/drier is recommended to be installed.
Outdoor Unit Installation
Make all connections to the outdoor unit with rain tight conduit
and fittings. Most building codes require a rain tight disconnect
switch at the outdoor unit as well (always check local codes). Run
the proper size copper wires to the unit, and connect as per the
manufacturer’s recommendations.
Ensure that the outdoor unit is setup for a TX system. If not, a
hard start kit may be required.
Wiring - Outdoor Unit
-32-
Module RPM
Refrigerant Module Installation (RPM-E) (2/5)
Module RPM Refrigerant Module Installation (RPM-E) (2/5)
Two L mounting brackets are shipped loose for attaching the
RPM-E to the fan coil, along with two sided foam tape for an
air seal between the units. When mounting the cooling coil to
the fancoil (Fig. RPM-04), ensure that no screws puncture the
drain pan or coil. It is advised that no screws be placed within
3 inches (76mm) from the bottom of the coil. This will prevent
the drain pan from being accidentally pierced. It is also advised
that care be taken when placing screws in the top left side of
the cooling coil (when looking at the access hatch), as this is
where the top most extent of the cooling coil is located. See
Specification Pages for the dimensions of the fan coil units and
cooling modules.
Mounting the RPM-E
Fig. RPM-04 - Mounting Brackets
(76mm)
(76mm)
(76mm)
(76mm)
P-Trap
Secondary drain pan