19

2.  Control valve does not regenerate 

A.  Transformer unplugged 

A.  Connect transformer

    automatically when REGEN button 

B.  No electric power at outlet 

B.  Repair outlet or use working outlet

    is depressed and held 

C.  Broken drive gear or drive cap assembly 

C.  Replace drive gear or drive cap assembly

     

D.  Defective PC board 

D.  Replace PC board 

 

 

 

3.  Control valve does not regenerate 

A.  Bypass valve in bypass position 

A.  Put control valve in service position

    automatically but does when 

B.   Meter connection disconnected 

B.  Connect meter to PC board

    REGEN button is depressed 

C.  Restricted/stalled meter turbine 

C.  Remove meter and check for free rotation

    

  

 

or foreign matter

     

D.   Defective meter 

D.  Replace meter

     

E.  Defective PC board 

E.  Replace PC board

     

F.  Programming error 

F.  Check control valve set-up procedure 

 

  4.  Time of day flashes on and off 

A.  Battery back-up maintains time-of-day up 

A.  Reset time of day and replace battery on PC Board

     

 

to 2 years in event of power outage and  

 

(Lithium coin type battery 2032)

     

 

battery is not depleted. Time of day flashes

     

 

when battery is depleted.

     

B.  Prior to 2/2007, PC board did not have  

B.  Reset time of day.

     

 

battery back-up - capacitor held time of day

     

 

up to 2 hours. Power outage > 2 hours.

 

  5.  Softener delivers hard water. 

A.  Bypass valve is open or faulty. 

A.  Close bypass valve or replace.

    

B.  No salt or low salt level in brine tank. 

B.  Add salt to brine tank and maintain salt level  

    

  

 

above water level.

     

C.  Softener fails to draw brine. 

C.  See problem #10.

     

D.  Excessive water usage. 

D.  Check gallon capacity settings.

     

E.  Insufficient brine level in brine tank. 

E.  Check  brine  refill  setting  and  refill  flow  restrictor  for   

 

    

  

 blockage.

     

F.   Resin level inadequate. 

F.  See problem #7. 

     

G.  Meter faulty. 

G.  Test meter and clean or replace meter.

     

H.  Raw water hardness fluctuation. 

H.  Test raw water hardness and adjust settings to 

 

    

  

 

highest known hardness.

 

  6.  Unit uses too much salt. 

A.  Improper brine refill setting. 

A.   Check  brine  refill  setting  for  proper  salt  dosage

 

     

B.  Improper settings. 

B.  Check water hardness and reevaluate capacity setting

 

     

 

 

 

specification

     

C.  Excessive water in brine tank. 

C.  See problem #9.

     

D.  Leaking faucets, toilets, etc... 

D.  Repair or replace those items.

     

E.  Brine line flow control out of place 

E.  Replace Brine line flow control.

 

 

7.  Loss of resin. 

A.  Backwash controller missing. 

A.  Install backwash controller.

     

B.  Faulty distributor tube assembly. 

B.  Check distributor tube assembly for cracks or holes.

     

C.  Air being drawn in through brine system. 

C.   Check  for  leaks  in  brine  lines,  fittings,  or  air  check. 

 

     

 

 

 

Repair or replace.

     

D.   Air in water supply system 

D.  1. Install upper distributor if missing.

     

 

   

 

2. Ensure that water supply system has an air 

    

  

 eliminator.

 

 

8.  Softener delivers salty water. 

A.  Low water pressure. 

A.  Check incoming water pressure - Must remain at  

 

     

 

 

 

minimum of 25 psi.

     

B.  Excessive water in brine tank. 

B.  See problem #9.

     

C.  Wrong size injector. 

C.  Install correct injector.

 

 

9.  Excessive water in brine tank. 

A.  Plugged injector. 

A.  Remove injector and clean ports.

     

B.  Faulty piston/seal assembly. 

B.  Replace piston/seal assembly.

     

C.  Plugged or kinked drain line. 

C.  Correct any kinking or plugging of drain line.

     

D.  Backwash flow controller closed off. 

D.  Check backwash flow controller.

     

E.  Defective brine line flow control. 

E.  Replace brine refill flow control.

10.  Softener fails to draw brine. 

A.  Injector is plugged, absent/missing oring(s) 

A.  Remove injector and clean ports/replace if necessary

     

B.  Faulty piston assembly. 

B.  Check piston assembly.

     

C.  Brine line connection leak. 

C.  Inspect brine line during refill cycle for leaks.

     

D.  Drain line plugged creating excess back pressure.  D.  Inspect drain line for blockage.

     

E.  Drain line too long or too high. 

E.  Refer to drain line specifications.

     

F.  Low inlet pressure. 

F.  Increase inlet pressure to a minimum of 25 psi.

11.  Continuous flow to drain. 

A.  Piston assembly failure. 

A.  Replace piston assembly.

     

B.  Motor failure. 

B.  Replace motor.

     

C.  Circuit board failure. 

C.  Replace circuit board.

12.  Loss of water pressure. 

A.  Iron build-up in resin. 

A.  See problem #13, page 23.

     

B.  Resin bed fouled with sand or sediment. 

B.  Rebed  softener  and  install  sediment  filter  ahead 

 

    

  

 

of softener.

     

C.  Resin bed mushing due to high amount 

C.  Rebed softener.  Install dechlorination system ahead

     

 

of oxidizers in water supply (chlorine). 

 

of softener

TROUBLE SHOOTING

 PROBLEM 

CAUSE 

CORRECTION

Содержание H-125 HE Series

Страница 1: ...vian Valley Road Waunakee Wisconsin 53597 www hellenbrand com info hellenbrand com p n 109122 Rev G Updated 8 30 18 2008 2018 System for Automatic Discharge Management U S Patent No 9 862 619 Method o...

Страница 2: ...g Conditions 4 Pre Installation Check List 5 Bypass Valve Operation 5 Water Softener Disinfection 5 Installation Instructions 6 Programming 7 16 Set Time of Day Softener Setup Service Reminder Diagnos...

Страница 3: ..._______________________________________________________ The average family uses 50 gallons per person daily for all water uses in the home about 30 gallons per person daily if soft water is not suppli...

Страница 4: ...uple of weeks initially to determine how much salt you use this will depend on how much water you use As a rule of thumb with 20 gpg hard water about a 1 2 lb of salt per person per day is used In oth...

Страница 5: ...a bypass valve Softening It is recommended that the conditioner be installed to soften both the hot and cold water supply A separate hard water faucet may be plumbed for drinking purposes if you desi...

Страница 6: ...itting Leave at least 6 between the drain line control fitting and solder joints when soldering pipes that are connected on the drain line control fitting Failure to do this could cause interior damag...

Страница 7: ...ys BACKWASH Keep in backwash until water once again runs clear at the drain 10 Press REGEN button again until RINSE is displayed Allow rinse cycle to run its full course While the rinse cycle is finis...

Страница 8: ...s sets the number of days between regenerations If value set to oFF regeneration initiation is based solely on gallons used If value is set as a number allowable range from 1 to 28 a regeneration init...

Страница 9: ...s of each cycle STEP 1S STEP 2S SOFTENING STEP 3S FILL 20 0 STEP 1S Press NEXT and simultaneously for 3 seconds If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated STE...

Страница 10: ...s capacity is affected by the fill time The grains capacity for the selected lbs salting should be confirmed by testing The capacity and hardness levels entered are used to automatically calculate res...

Страница 11: ...ps registering flow which ever comes first Press NEXT to go to 19S for programming Service Alarm Relay activates on service alarm setting gallons time or both see step 21S Relay Triggered for Lockout...

Страница 12: ...down arrows to select start time into regeneration to energize relay regeneration is defined by start of backwash or draw whatever comes first Range 20 500 minutes or select REGEN Select REGEN if rel...

Страница 13: ...URN TO NORMAL MODE DIAGNOSTICS STEP 2D 2 DAYS SINCE REGEN STEP 3D 342 GAL STEP 1D DAY SINCE LAST REGEN STEP 1D Press or simultaneously for three seconds If screen in step 2D does not appear in 5 secon...

Страница 14: ...on out is designated by sign Any time MAV is rebuilt or replaced reset diagnostics to reflect new drive characteristics STEP 6D 12 7 RETURN TO NORMAL MODE STEP 5D USAGE HISTORY DAY 108GAL GAL MAX FLOW...

Страница 15: ...1 25 SET STEP 3CS OFF ALTERNATOR SYSTEM SET VALVE TYPE ALT A ALTERNATOR SYSTEM SET STEP 4CS STEP 5CS REFRESH RINSE SET TYPE MIN STEP 4CS Twin Alternating System Allows automatic alternation between t...

Страница 16: ...ntrol Valve for Separate Source Operation Select Separate Source Enabled for control operation For separate source opera tion the three wire connector is not used Selection requires that a connection...

Страница 17: ...fill flow control retainer assembly from the elbow Reinstall the elbow assembly and secure with the locking clip Disconnect the brine tube at the top of the salt keeper and force air into the brine tu...

Страница 18: ...ans former if inadequate voltage 4 Low battery after power outage D1 If power outage occurred and battery on board has low voltage the microprocessor may not recover cleanly and display properly Disco...

Страница 19: ...specification C Excessive water in brine tank C See problem 9 D Leaking faucets toilets etc D Repair or replace those items E Brine line flow control out of place E Replace Brine line flow control 7 L...

Страница 20: ...eter D Unplug meter from PC board if LED display lights appropriately replace meter E Defective PC board E Replace PC board 15 Control does not display correct A Power outage 2 years A Reset time of d...

Страница 21: ...SBV 8 Grid 1 104421 c 18X40 w 474 SBV 11 Grid 1 104423 d 24x50 w 474 SBV 6 Grid 1 104428 e 24x50 w 474 SBV 9 Grid 1 104423 f 18x40 w 474 SBV No Grid 1 104416 g 24x50 w 474 SBV No Grid 1 104426 h 30x50...

Страница 22: ...H125 PC Board 1 5 101746 Drive Gear 12x36 3 6 101459 Drive Gear Cover 1 Not Shown 103723 Optional Relay Kit PCM 1 Not Shown 103729 Optional Relay Kit 120V Pigtail Not Shown 101880 Auxiliary Switch Ki...

Страница 23: ...Plug 1 101825 Injector Assembly A Black 101826 Injector Assembly B Brown 101827 Injector Assembly C Violet 101828 Injector Assembly D Red 101829 Injector Assembly E White 5 101830 Injector Assembly F...

Страница 24: ...ystems 1 102322 H125 H150 Refill Port Plug Assy 1 2 101154 H125 H150 BLFC Adapter 1 3 101414 Locking Clip 1 4 102417 H125 H150 Refill Retainer Assy 1 4 8 103590 1 2 Refill Elbow Assy 1 5 102153 O Ring...

Страница 25: ...ine oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec tion Teflon tape is not necess...

Страница 26: ...ss Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 10...

Страница 27: ...with a hammer Do not use vaseline oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec...

Страница 28: ...28 FLOW DIAGRAMS SERVICE AND BACKWASH FLOW DIAGRAMS RINSE AND FILL...

Страница 29: ...or disassemble the valve the wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly Wrench part number is 102892 Loosens Drain Nut in Polytube Applications L...

Страница 30: ...n gallons capacity reaches 0 Time of regeneration will not be allowed to be set because of regeneration will always occur when gallons capacity reaches 0 DELAY IMMEDIATE oFF Reserve capacity not autom...

Страница 31: ...board The drive gear cover is held in place on the drive bracket by three clips The largest of the three clips is always orientated to the bottom of the drive bracket With the PC board facing up push...

Страница 32: ...force the spacer stack assembly in The control valve body bore interior can be lubricated with silicone to allow for easy insertion of the entire stack Do not use silicone or any other type of lubric...

Страница 33: ...urbine to remove it from the shaft Do not use a wire brush to clean the turbine Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar The turbine can be immersed in the che...

Страница 34: ...34 SERVICE RATES PRESSURE DROP CHARTS...

Страница 35: ...e Tank NO NO NO NO NO NO NO 3 8 3 8 3 8 3 8 3 8 3 8 3 8 2 2 2 2 4 2 4 2 5 3 7 5 7 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 D RED E WHITE G YELLOW H GREEN I ORANGE J LT BLUE K LT GREEN 0 22 0 27 0 46 0 46 0 56 0...

Страница 36: ...RANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act of God misuse misap plication neglect alteration installation or operation contrary to Hellenbrand s pr...

Отзывы: