10
STEP 4 S –
Select the time for the second cycle
(which in this example is SOFTENING)
using
or
button. Press NEXT to go to Step 5S. Press REGEN to return to the previous
step.
STEP 5 S –
Select the time for the third cycle
(which in this example is BACKWASH) using
the
or
button. Press NEXT to go to Step 6S. Press REGEN to return to the previous
step.
STEP 6 S –
Select the time for the fourth cycle
(which in this example is BRINE DRAW)
using the
or
button. Press NEXT to go to Step 7S. Press REGEN to return to the
previous step.
STEP 7 S – Select the time for the fifth cycle
(which in this example is Second BACKWASH)
using the
or
button. Press NEXT to go to Step 8S. Press REGEN to return to the
previous step.
STEP 8 S –
Select the time for the sixth cycle
(which in this example is RINSE) using the
or
button. Press NEXT to go to Step 9S. Press REGEN to return to the previous step.
STEP 9 S
-
Set Grain Capacity
using the
or
button. The ion exchange capacity is in
grains of hardness as calcium carbonate for the system based on the pounds of salt that will
be used. The allowable grains capacity range varies from 5,000 to 3,000,000 grains. The
increment increase is 500 for the range from 5000 to 30,000; 1000 for the range of 30,000 to
100,000; and 2000 for the range of 100,000 to 3,000,000. Grains capacity is affected by the
fill time. The grains capacity for the selected lbs. salting should be confirmed by testing. The
capacity and hardness levels entered are used to automatically calculate reserve capacity
when gallon capacity is set to AUTO.
Factory setting is the capacity of the softener at
medium salting.
See Page 43. Press NEXT to go to Step 10S. Press REGEN to return to
previous step.
STEP 10 S –
Set Gallons Capacity
using
or
button. If value is set to:
• “AUTO” gallon capacity will be automatically calculated and reserve capacity will be
automatically estimated;
• “oFF” regeneration will be based solely on the day override set (see Installer Display/Settings
Step 3, page 8 / proportional brining will not function if OFF selected); or
• as a number of gallons (allowable range 20 to 1,500,000) regeneration will be based on the
value specified.
Increment increase is 20 for the range 20 to 2000, 100 for the range of 2000 to 10,000 and
500 for the range of 10,000 to 50,000 and 2000 for range of 50,000 to 1,500,000.
If “oFF” or a number is used, hardness cannot be set in Installer Displays/Settings Step 2,
page 8. See page 35 for more detail.
Factory Setting is AUTO.
Press NEXT to go to Step
11 S. Press REGEN to return to previous step.
STEP 4S
SOFTENING TIME
120:00
MIN
STEP 5S
SET
8:00
MIN
BACKWASH TIME
STEP 6S
SET
60:00
MIN
DRAW TIME
STEP 7S
SET
BACKWASH TIME
STEP 8S
RINSE TIME
STEP 9S
GRAIN OF CAPACITY
64.0
x1K
STEP 10S
RESERVE CALCULATOR
AUTO
SET
SET
8:00
SET
MIN
4:00
SET
MIN
➔
➔
➔
➔
➔
➔
➔