background image

5

Water Pressure:

 A minimum of 25 pounds of water pressure 

(psi) is required for regeneration.  Maximum 125 psi.

Water Quality:

 On rural water supplies there is often a problem 

with sand or sediment in the water. (This problem occasionally 

occurs in public water supplies also.) If the water is not filtered 

before being softened, the sand and sediment will plug up the 

water softener restricting the flow through the resin bed. This 

problem often requires rebedding of the mineral tank. 

Note:

 Well 

and/or pump problems affecting the operation of the softener 

are repairs that are not covered under warranty. To prevent these 

unnecessary, and expensive repairs not covered under warranty, 

we recommend the installation of an in-line filter system ahead 

of the softener.

Electrical:

 A  continuous  110  volt,  60  cycle  current  supply  is 

required. 

Make certain the current supply is uninterrupted and 

cannot be turned off with another switch.  All electrical connec-

tions must be connected per local codes.  

Surge protection is 

recommended with all electronic controls.

Existing Plumbing:

  Condition  of  existing  plumbing  must  be 

free from lime and iron build-up. Piping that is built-up heavily 

with lime and/or iron must be replaced. If piping is blocked with 

iron, additional equipment must be installed ahead of the water 

conditioner to correct the problem.

Drain Line:

 The conditioner should be located close to a drain. 

Avoid overhead drain lines if possible to prevent back pressure 

on the brine injector. Overhead drains are not to exceed 8 feet 

above the floor and no more than 20 feet in length.  The pipe 

size for the drain line should be a minimum of 3/4”.  Backwash 

flow rates in excess of 7 gpm or length in excess of 20’ require 

1” drain line.

Bypass Valves:

 Always provide for the installation of a bypass 

valve. 

Softening:

 It is recommended that the conditioner be installed 

to soften both the hot and cold water supply. A separate hard 

water faucet may be plumbed for drinking purposes if you desire. 

Outside faucets should be left on hard water.

Caution:

 Water temperature is not to exceed 110°F; the condi

-

tioner cannot be subject to freezing conditions, or to a vacuum 

due to loss of pressure (such as a water main break).

PRE-INSTALLATION CHECK LIST

(All electrical & plumbing should be done in accordance to all local codes)

Figure 6

Figure 5

Figure 3

Figure 4

BYPASS VALVE OPERATION

WATER SOFTENER DISINFECTION

The construction materials of your water softener will not support 

bacterial growth nor will these materials contaminate a water 

supply. However, the normal conditions existing during shipping, 

storage, and installation indicate the advisability of disinfecting 

a softener after installation, before the softener is used to treat 

potable water. In addition, during normal use a softener may 

become fouled with organic matter or in some cases, with bac-

teria from the water supply.

 

Therefore, every water softener should be disinfected after 

installation, some will require periodic disinfection during their 

normal life. You have two choices for disinfection as follows:
A.   SODIUM HYPOCHLORITE (household bleach)

  5.25% 

SODIUM HYPOCHLORITE

 solutions are available 

under such trade names such as Clorox, Linco, Bo Peep, 

White Sail and Eagle Brand Bleach. If stronger solutions are 

used, such as those sold for commercial laundries, adjust 

the dosage accordingly.

    1. Dosage:

      a. Softening  resin;  1.2  fluid  ounce  per  cubic  foot  of 

 

   resin.

    2. Add the required amount of hypochlorite solution to the  

      brine well of the brine tank.

   a. Proceed with the normal regeneration.  Press REGEN

and allow the water softener to go through a normal

   regeneration.

B.   EPA and NSF approved Sani-System by Pro Products.   

    This can be purchased from your water treatment provider

    or at: http://proproducts.com/products/sani-system.

Содержание H-125 HE Series

Страница 1: ...vian Valley Road Waunakee Wisconsin 53597 www hellenbrand com info hellenbrand com p n 109122 Rev G Updated 8 30 18 2008 2018 System for Automatic Discharge Management U S Patent No 9 862 619 Method o...

Страница 2: ...g Conditions 4 Pre Installation Check List 5 Bypass Valve Operation 5 Water Softener Disinfection 5 Installation Instructions 6 Programming 7 16 Set Time of Day Softener Setup Service Reminder Diagnos...

Страница 3: ..._______________________________________________________ The average family uses 50 gallons per person daily for all water uses in the home about 30 gallons per person daily if soft water is not suppli...

Страница 4: ...uple of weeks initially to determine how much salt you use this will depend on how much water you use As a rule of thumb with 20 gpg hard water about a 1 2 lb of salt per person per day is used In oth...

Страница 5: ...a bypass valve Softening It is recommended that the conditioner be installed to soften both the hot and cold water supply A separate hard water faucet may be plumbed for drinking purposes if you desi...

Страница 6: ...itting Leave at least 6 between the drain line control fitting and solder joints when soldering pipes that are connected on the drain line control fitting Failure to do this could cause interior damag...

Страница 7: ...ys BACKWASH Keep in backwash until water once again runs clear at the drain 10 Press REGEN button again until RINSE is displayed Allow rinse cycle to run its full course While the rinse cycle is finis...

Страница 8: ...s sets the number of days between regenerations If value set to oFF regeneration initiation is based solely on gallons used If value is set as a number allowable range from 1 to 28 a regeneration init...

Страница 9: ...s of each cycle STEP 1S STEP 2S SOFTENING STEP 3S FILL 20 0 STEP 1S Press NEXT and simultaneously for 3 seconds If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated STE...

Страница 10: ...s capacity is affected by the fill time The grains capacity for the selected lbs salting should be confirmed by testing The capacity and hardness levels entered are used to automatically calculate res...

Страница 11: ...ps registering flow which ever comes first Press NEXT to go to 19S for programming Service Alarm Relay activates on service alarm setting gallons time or both see step 21S Relay Triggered for Lockout...

Страница 12: ...down arrows to select start time into regeneration to energize relay regeneration is defined by start of backwash or draw whatever comes first Range 20 500 minutes or select REGEN Select REGEN if rel...

Страница 13: ...URN TO NORMAL MODE DIAGNOSTICS STEP 2D 2 DAYS SINCE REGEN STEP 3D 342 GAL STEP 1D DAY SINCE LAST REGEN STEP 1D Press or simultaneously for three seconds If screen in step 2D does not appear in 5 secon...

Страница 14: ...on out is designated by sign Any time MAV is rebuilt or replaced reset diagnostics to reflect new drive characteristics STEP 6D 12 7 RETURN TO NORMAL MODE STEP 5D USAGE HISTORY DAY 108GAL GAL MAX FLOW...

Страница 15: ...1 25 SET STEP 3CS OFF ALTERNATOR SYSTEM SET VALVE TYPE ALT A ALTERNATOR SYSTEM SET STEP 4CS STEP 5CS REFRESH RINSE SET TYPE MIN STEP 4CS Twin Alternating System Allows automatic alternation between t...

Страница 16: ...ntrol Valve for Separate Source Operation Select Separate Source Enabled for control operation For separate source opera tion the three wire connector is not used Selection requires that a connection...

Страница 17: ...fill flow control retainer assembly from the elbow Reinstall the elbow assembly and secure with the locking clip Disconnect the brine tube at the top of the salt keeper and force air into the brine tu...

Страница 18: ...ans former if inadequate voltage 4 Low battery after power outage D1 If power outage occurred and battery on board has low voltage the microprocessor may not recover cleanly and display properly Disco...

Страница 19: ...specification C Excessive water in brine tank C See problem 9 D Leaking faucets toilets etc D Repair or replace those items E Brine line flow control out of place E Replace Brine line flow control 7 L...

Страница 20: ...eter D Unplug meter from PC board if LED display lights appropriately replace meter E Defective PC board E Replace PC board 15 Control does not display correct A Power outage 2 years A Reset time of d...

Страница 21: ...SBV 8 Grid 1 104421 c 18X40 w 474 SBV 11 Grid 1 104423 d 24x50 w 474 SBV 6 Grid 1 104428 e 24x50 w 474 SBV 9 Grid 1 104423 f 18x40 w 474 SBV No Grid 1 104416 g 24x50 w 474 SBV No Grid 1 104426 h 30x50...

Страница 22: ...H125 PC Board 1 5 101746 Drive Gear 12x36 3 6 101459 Drive Gear Cover 1 Not Shown 103723 Optional Relay Kit PCM 1 Not Shown 103729 Optional Relay Kit 120V Pigtail Not Shown 101880 Auxiliary Switch Ki...

Страница 23: ...Plug 1 101825 Injector Assembly A Black 101826 Injector Assembly B Brown 101827 Injector Assembly C Violet 101828 Injector Assembly D Red 101829 Injector Assembly E White 5 101830 Injector Assembly F...

Страница 24: ...ystems 1 102322 H125 H150 Refill Port Plug Assy 1 2 101154 H125 H150 BLFC Adapter 1 3 101414 Locking Clip 1 4 102417 H125 H150 Refill Retainer Assy 1 4 8 103590 1 2 Refill Elbow Assy 1 5 102153 O Ring...

Страница 25: ...ine oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec tion Teflon tape is not necess...

Страница 26: ...ss Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 10...

Страница 27: ...with a hammer Do not use vaseline oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec...

Страница 28: ...28 FLOW DIAGRAMS SERVICE AND BACKWASH FLOW DIAGRAMS RINSE AND FILL...

Страница 29: ...or disassemble the valve the wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly Wrench part number is 102892 Loosens Drain Nut in Polytube Applications L...

Страница 30: ...n gallons capacity reaches 0 Time of regeneration will not be allowed to be set because of regeneration will always occur when gallons capacity reaches 0 DELAY IMMEDIATE oFF Reserve capacity not autom...

Страница 31: ...board The drive gear cover is held in place on the drive bracket by three clips The largest of the three clips is always orientated to the bottom of the drive bracket With the PC board facing up push...

Страница 32: ...force the spacer stack assembly in The control valve body bore interior can be lubricated with silicone to allow for easy insertion of the entire stack Do not use silicone or any other type of lubric...

Страница 33: ...urbine to remove it from the shaft Do not use a wire brush to clean the turbine Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar The turbine can be immersed in the che...

Страница 34: ...34 SERVICE RATES PRESSURE DROP CHARTS...

Страница 35: ...e Tank NO NO NO NO NO NO NO 3 8 3 8 3 8 3 8 3 8 3 8 3 8 2 2 2 2 4 2 4 2 5 3 7 5 7 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 D RED E WHITE G YELLOW H GREEN I ORANGE J LT BLUE K LT GREEN 0 22 0 27 0 46 0 46 0 56 0...

Страница 36: ...RANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act of God misuse misap plication neglect alteration installation or operation contrary to Hellenbrand s pr...

Отзывы: