background image

17

1.  

Salt Usage: See your water conditioning professional for a rec

-

ommendation on the best type of salt for your application.

2.  Brine Tank Cleaning:

a.  Remove brine tank cover.

b.  Scoop out as much old salt as possible.

c.  Disconnect brine tubing from safety brine valve at brine well.

d.  Remove safety brine valve from brine well.

e.  Place one hand in brine well to hold overflow nut and  

 

remove 2 piece overflow.

  

f.  Remove optional brine well and grid plate, if used,  

 

  from brine tank.

  g. 

Remove any remaining salt and/or impurities from brine  

   tank.

 h. 

Using clean water and a brush or rag, wipe and rinse  

   inside 

of brine tank.  Also wipe and rinse the grid plate and  

 

  brine well.

i.  Reassemble brine tank reversing steps c - f.  Note: If grid  

 

plate is used and it is damaged or cracked, replace 

  

with new one.

j.   Put brine tank in place making sure there is no debris or  

 

foreign material beneath it.

k.  Reconnect brine tubing to safety brine valve.

l.  Manually add 6 inches of water to the brine tank (or to  

 

approximately 1” above the grid plate, if used).

m.   Add new salt.  Important:  Do not add the old salt which  

  was removed earlier unless it is clean and not mushy.   

 

We recommend using new salt.

n.  Follow the disinfection instructions found on page 5.

o.   Put on brine tank cover. 

MISCELLANEOUS

In cold weather climates it is common for plumbing systems that 

are not in use to be “winterized“ or drained of all water to prevent 

any damage that may be caused by the excessive expansion of 

water when it freezes. To prevent damage to a water softener it 

must be 

properly

 drained also. A simple way to properly drain 

or winterize a water softener is to use compressed air to force 

all of the water out of the softener mineral tank. The following 

procedure will explain the process:

1)  Initiate the softener into a manual regeneration cycle.  Advance 

control to backwash and allow it to complete the backwash 

cycle (this will clean the media) and start into the brine-draw 

cycle. Note: Be sure there is salt in the brine tank and water 

has been in contact with salt at least 20 minutes.  Allow the 

regeneration to continue in the brine draw cycle until the 

brine is drawn out of the salt keeper and the air check at 

the bottom of the brine pick-up tube shuts off. At this time 

no more brine is introduced into the softener and the slow 

rinse process begins.

2)  Turn the water supply inlet and outlet valves off to the water 

softener as soon as the air check shuts off and no more brine 

is being drawn into the softener (at the beginning of the slow 

rinse process). 

3)  Unplug the electric power leaving the softener control valve 

in the brine draw cycle.

4)  Remove  the  brine  refill  elbow  assembly  from  the  control 

valve.  Remove the refill flow control retainer assembly from 

the elbow.  Reinstall the elbow assembly and secure with the 

locking clip.  Disconnect the brine tube at the top of the salt 

keeper and force air into the brine tube toward the softener 

mineral tank and control valve. The air will force the brine/

water solution that was drawn into the mineral tank out to 

drain through the control valve drain line. (An air compressor 

blow gun attachment with a portable air compressor works 

well.)  Reinstall the brine line flow control retainer in side 

of the refill elbow assembly.  Reinstall the brine refill elbow 

assembly and secure with locking clip.

  CAUTION

: You do not want to apply any more pressure than 

necessary to force the brine/water out of the mineral tank. 

  The small amount of brine/water that may be left in the 

mineral tank will not expand enough to cause any damage 

to the softener when it freezes.

  If your softener is equipped with an optional bottom drain 

on the mineral tank, you will have to follow all of the same 

procedures with the exception of the need for compressed 

air. With the brine tube disconnected from the salt keeper, 

raise it to a level above the softener control valve and tem-

porarily secure it in this position. Now open the drain valve 

at the bottom of the mineral tank and allow  all brine/water 

to drain from the mineral tank.

  CAUTION:

  If a hose is connected to the drain valve to direct 

the brine/water to a floor drain be sure it runs downward 

and is unobstructed. When brine/water quits running at the 

drain, be sure to leave the drain valve open until you start 

the system up again.

5)  At this time the salt keeper has very little water left in it. What 

liquid is left in the salt keeper is saturated brine, provided 

that there is still salt left in the tank. Saturated brine will not 

freeze solid and cause any damage and does not have to 

be drained any further from the brine tank.

  If there is no salt left in the salt keeper when the system is 

drained we recommend dumping all of the water out of the 

brine tank at this time. See brine tank cleaning instructions. 

(#2 in miscellaneous section, below)

6) 

CAUTION:

 It is important at this time to be assured that the 

inlet/outlet water supply piping is properly drained. Depend

-

ing on how the water supply piping was routed to the water 

softener control valve, a water loop or trap may have been 

created.

  Sometimes drain valve(s) are installed at the bottom of the 

loop to assure all water can be drained out. If not it may be 

necessary to disconnect the control valve from the piping 

system and open the inlet/outlet valve(s) to allow all the water 

to drain from the piping. This should be done when the rest 

of the plumbing system is drained.

7)  Draining or winterizing of your softener is complete. Refer 

to the start-up procedures on page 7 when you are ready to 

start your softener.

WATER SOFTENER DRAINING PROCEDURE

Содержание H-125 HE Series

Страница 1: ...vian Valley Road Waunakee Wisconsin 53597 www hellenbrand com info hellenbrand com p n 109122 Rev G Updated 8 30 18 2008 2018 System for Automatic Discharge Management U S Patent No 9 862 619 Method o...

Страница 2: ...g Conditions 4 Pre Installation Check List 5 Bypass Valve Operation 5 Water Softener Disinfection 5 Installation Instructions 6 Programming 7 16 Set Time of Day Softener Setup Service Reminder Diagnos...

Страница 3: ..._______________________________________________________ The average family uses 50 gallons per person daily for all water uses in the home about 30 gallons per person daily if soft water is not suppli...

Страница 4: ...uple of weeks initially to determine how much salt you use this will depend on how much water you use As a rule of thumb with 20 gpg hard water about a 1 2 lb of salt per person per day is used In oth...

Страница 5: ...a bypass valve Softening It is recommended that the conditioner be installed to soften both the hot and cold water supply A separate hard water faucet may be plumbed for drinking purposes if you desi...

Страница 6: ...itting Leave at least 6 between the drain line control fitting and solder joints when soldering pipes that are connected on the drain line control fitting Failure to do this could cause interior damag...

Страница 7: ...ys BACKWASH Keep in backwash until water once again runs clear at the drain 10 Press REGEN button again until RINSE is displayed Allow rinse cycle to run its full course While the rinse cycle is finis...

Страница 8: ...s sets the number of days between regenerations If value set to oFF regeneration initiation is based solely on gallons used If value is set as a number allowable range from 1 to 28 a regeneration init...

Страница 9: ...s of each cycle STEP 1S STEP 2S SOFTENING STEP 3S FILL 20 0 STEP 1S Press NEXT and simultaneously for 3 seconds If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated STE...

Страница 10: ...s capacity is affected by the fill time The grains capacity for the selected lbs salting should be confirmed by testing The capacity and hardness levels entered are used to automatically calculate res...

Страница 11: ...ps registering flow which ever comes first Press NEXT to go to 19S for programming Service Alarm Relay activates on service alarm setting gallons time or both see step 21S Relay Triggered for Lockout...

Страница 12: ...down arrows to select start time into regeneration to energize relay regeneration is defined by start of backwash or draw whatever comes first Range 20 500 minutes or select REGEN Select REGEN if rel...

Страница 13: ...URN TO NORMAL MODE DIAGNOSTICS STEP 2D 2 DAYS SINCE REGEN STEP 3D 342 GAL STEP 1D DAY SINCE LAST REGEN STEP 1D Press or simultaneously for three seconds If screen in step 2D does not appear in 5 secon...

Страница 14: ...on out is designated by sign Any time MAV is rebuilt or replaced reset diagnostics to reflect new drive characteristics STEP 6D 12 7 RETURN TO NORMAL MODE STEP 5D USAGE HISTORY DAY 108GAL GAL MAX FLOW...

Страница 15: ...1 25 SET STEP 3CS OFF ALTERNATOR SYSTEM SET VALVE TYPE ALT A ALTERNATOR SYSTEM SET STEP 4CS STEP 5CS REFRESH RINSE SET TYPE MIN STEP 4CS Twin Alternating System Allows automatic alternation between t...

Страница 16: ...ntrol Valve for Separate Source Operation Select Separate Source Enabled for control operation For separate source opera tion the three wire connector is not used Selection requires that a connection...

Страница 17: ...fill flow control retainer assembly from the elbow Reinstall the elbow assembly and secure with the locking clip Disconnect the brine tube at the top of the salt keeper and force air into the brine tu...

Страница 18: ...ans former if inadequate voltage 4 Low battery after power outage D1 If power outage occurred and battery on board has low voltage the microprocessor may not recover cleanly and display properly Disco...

Страница 19: ...specification C Excessive water in brine tank C See problem 9 D Leaking faucets toilets etc D Repair or replace those items E Brine line flow control out of place E Replace Brine line flow control 7 L...

Страница 20: ...eter D Unplug meter from PC board if LED display lights appropriately replace meter E Defective PC board E Replace PC board 15 Control does not display correct A Power outage 2 years A Reset time of d...

Страница 21: ...SBV 8 Grid 1 104421 c 18X40 w 474 SBV 11 Grid 1 104423 d 24x50 w 474 SBV 6 Grid 1 104428 e 24x50 w 474 SBV 9 Grid 1 104423 f 18x40 w 474 SBV No Grid 1 104416 g 24x50 w 474 SBV No Grid 1 104426 h 30x50...

Страница 22: ...H125 PC Board 1 5 101746 Drive Gear 12x36 3 6 101459 Drive Gear Cover 1 Not Shown 103723 Optional Relay Kit PCM 1 Not Shown 103729 Optional Relay Kit 120V Pigtail Not Shown 101880 Auxiliary Switch Ki...

Страница 23: ...Plug 1 101825 Injector Assembly A Black 101826 Injector Assembly B Brown 101827 Injector Assembly C Violet 101828 Injector Assembly D Red 101829 Injector Assembly E White 5 101830 Injector Assembly F...

Страница 24: ...ystems 1 102322 H125 H150 Refill Port Plug Assy 1 2 101154 H125 H150 BLFC Adapter 1 3 101414 Locking Clip 1 4 102417 H125 H150 Refill Retainer Assy 1 4 8 103590 1 2 Refill Elbow Assy 1 5 102153 O Ring...

Страница 25: ...ine oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec tion Teflon tape is not necess...

Страница 26: ...ss Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 10...

Страница 27: ...with a hammer Do not use vaseline oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec...

Страница 28: ...28 FLOW DIAGRAMS SERVICE AND BACKWASH FLOW DIAGRAMS RINSE AND FILL...

Страница 29: ...or disassemble the valve the wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly Wrench part number is 102892 Loosens Drain Nut in Polytube Applications L...

Страница 30: ...n gallons capacity reaches 0 Time of regeneration will not be allowed to be set because of regeneration will always occur when gallons capacity reaches 0 DELAY IMMEDIATE oFF Reserve capacity not autom...

Страница 31: ...board The drive gear cover is held in place on the drive bracket by three clips The largest of the three clips is always orientated to the bottom of the drive bracket With the PC board facing up push...

Страница 32: ...force the spacer stack assembly in The control valve body bore interior can be lubricated with silicone to allow for easy insertion of the entire stack Do not use silicone or any other type of lubric...

Страница 33: ...urbine to remove it from the shaft Do not use a wire brush to clean the turbine Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar The turbine can be immersed in the che...

Страница 34: ...34 SERVICE RATES PRESSURE DROP CHARTS...

Страница 35: ...e Tank NO NO NO NO NO NO NO 3 8 3 8 3 8 3 8 3 8 3 8 3 8 2 2 2 2 4 2 4 2 5 3 7 5 7 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 D RED E WHITE G YELLOW H GREEN I ORANGE J LT BLUE K LT GREEN 0 22 0 27 0 46 0 46 0 56 0...

Страница 36: ...RANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act of God misuse misap plication neglect alteration installation or operation contrary to Hellenbrand s pr...

Отзывы: