STEP 11 S – Set Regeneration Time Options 

using the 

 

or 

 button. If value is set to:

• “DELAY” means regeneration will occur at the preset time; (page 8, step 4)

• “IMMEDIATE” means regeneration will occur immediately when the gallons capacity reaches 0 (zero); or

• “DELAY + IMMEDIATE” means regeneration will occur at one of the following:

- the preset time when the gallons capacity falls below the reserve or the specified number of days be

-

tween regenerations is reached, whichever comes first; or

- immediately after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).

-Delay + Immediate is NOT available if control is programmed as a twin alternating configuration.  Select

-

ing "DELAY" will result in an immediate alternation upon capacity depletion but regeneration is delayed to 

preset time.

See page 33 for more options.  

Factory Setting is DELAY + IMMEDIATE. 

 Press NEXT to go to Step 12S.  

Press REGEN to return to previous step.

STEP 12 S –

 

Set Relay to activate by Time, Gallons, Regen Gallons, Lockout, Off or 

Service Alarm

 by using 

 

or 

 buttons.  A relay can be used to operate a chemical feed pump or sole

-

noid, etc.  The choices are:

  •  Relay Triggered on Time - Relay activates after set number of minutes after start of regeneration.  Start of 

regeneration is defined by first backwash cycle, dn brine or up brine, whichever is first.  Relay deacti

-

vates after set time. Press NEXT for programming.

  •  Relay Triggered on Gallons - Relay activates every set number of gallons while in service and deacti-

vates after set time.  Press NEXT to go to 16S for programming.

  •  Relay Triggered on Regen Gallons - Relay activates after set number of gallons in service 

or

 gallons 

used during regeneration and de-activates after set time or when meter stops registering flow, which

-

ever comes first.  Press NEXT to go to 19S for programming.

  •  Service Alarm

 - Relay activates on service alarm setting: gallons, time or both, see step 21S.

  • 

Relay Triggered for Lockout 

- Relay is activated at set number of minutes into regeneration including 

negative numbers to energize relay prior to regeneration starting.  Selection of energizing relay for 

complete regeneration cycle is available by selecting REGEN for time setting, see step 22S.

  •  

Off

 - If off is selected, Steps 13S – 24S will not be shown.  

Factory setting = OFF

.  Press NEXT to 

go to step 13S or other selection for relay settings, or 25S if OFF selected.

STEP 11S

DELAY + IMMEDIATE  

REGEN

SET   

RELAY 1 DURATION  

STEP 13S

RELAY 1 SET POINT

10

MIN

RELAY 1 DURATION

3:00

MIN

STEP 14S

RELAY 1 SETPOINT  

GAL

1

SET   

STEP 12S

RELAY 1 "TIME" 

TRIGGER

SET   

SET   

SET   

SET   

0:01

MIN

RELAY 1 "GALLONS" 

TRIGGER

SET   

STEP 15S

STEP 17S

STEP 16S

STEP 13 S –

 If off was selected in previous step, this screen does not appear.   

Time chosen to Activate Relay,

 use up and down arrows to set # of minutes 

AFTER START OF REGEN to activate relay. 

Start of regeneration is defined as 

first Backwash or Regenerant Draw mode.  Time Range = 1 – 500 minutes. Press 

NEXT to go to Step 14S.

STEP 14 S – 

Use Up and Down arrows to set duration of relay activation in minutes.  

Range is 0:01 (1 second) to 500:00 (500 minutes).  Press NEXT to go to Step 25S.  

Press REGEN to return to previous step.

STEP 16 S – 

Use up and down arrows to set # of gallons per relay activation.  

Range = 0.1 – 20,000 gallons.   Press NEXT for Relay Duration.  Press REGEN to 

return to previous step. 

STEP 17 S – 

Use up and down arrows to set duration of relay activation in minutes.  

Range = 0:01 (1 second) - 500:00 (500 minutes).  Press NEXT to go to Step 25S.  

Press REGEN to return to previous step.

STEP 15 S –

 

Gallons chosen to activate relay.

 If Off or Time was selected in previous steps, this screen 

does not appear.  Press NEXT for trigger programming.

Содержание H-125 HE Series

Страница 1: ...vian Valley Road Waunakee Wisconsin 53597 www hellenbrand com info hellenbrand com p n 109122 Rev G Updated 8 30 18 2008 2018 System for Automatic Discharge Management U S Patent No 9 862 619 Method o...

Страница 2: ...g Conditions 4 Pre Installation Check List 5 Bypass Valve Operation 5 Water Softener Disinfection 5 Installation Instructions 6 Programming 7 16 Set Time of Day Softener Setup Service Reminder Diagnos...

Страница 3: ..._______________________________________________________ The average family uses 50 gallons per person daily for all water uses in the home about 30 gallons per person daily if soft water is not suppli...

Страница 4: ...uple of weeks initially to determine how much salt you use this will depend on how much water you use As a rule of thumb with 20 gpg hard water about a 1 2 lb of salt per person per day is used In oth...

Страница 5: ...a bypass valve Softening It is recommended that the conditioner be installed to soften both the hot and cold water supply A separate hard water faucet may be plumbed for drinking purposes if you desi...

Страница 6: ...itting Leave at least 6 between the drain line control fitting and solder joints when soldering pipes that are connected on the drain line control fitting Failure to do this could cause interior damag...

Страница 7: ...ys BACKWASH Keep in backwash until water once again runs clear at the drain 10 Press REGEN button again until RINSE is displayed Allow rinse cycle to run its full course While the rinse cycle is finis...

Страница 8: ...s sets the number of days between regenerations If value set to oFF regeneration initiation is based solely on gallons used If value is set as a number allowable range from 1 to 28 a regeneration init...

Страница 9: ...s of each cycle STEP 1S STEP 2S SOFTENING STEP 3S FILL 20 0 STEP 1S Press NEXT and simultaneously for 3 seconds If screen in Step 2S does not appear in 5 seconds the lock on the valve is activated STE...

Страница 10: ...s capacity is affected by the fill time The grains capacity for the selected lbs salting should be confirmed by testing The capacity and hardness levels entered are used to automatically calculate res...

Страница 11: ...ps registering flow which ever comes first Press NEXT to go to 19S for programming Service Alarm Relay activates on service alarm setting gallons time or both see step 21S Relay Triggered for Lockout...

Страница 12: ...down arrows to select start time into regeneration to energize relay regeneration is defined by start of backwash or draw whatever comes first Range 20 500 minutes or select REGEN Select REGEN if rel...

Страница 13: ...URN TO NORMAL MODE DIAGNOSTICS STEP 2D 2 DAYS SINCE REGEN STEP 3D 342 GAL STEP 1D DAY SINCE LAST REGEN STEP 1D Press or simultaneously for three seconds If screen in step 2D does not appear in 5 secon...

Страница 14: ...on out is designated by sign Any time MAV is rebuilt or replaced reset diagnostics to reflect new drive characteristics STEP 6D 12 7 RETURN TO NORMAL MODE STEP 5D USAGE HISTORY DAY 108GAL GAL MAX FLOW...

Страница 15: ...1 25 SET STEP 3CS OFF ALTERNATOR SYSTEM SET VALVE TYPE ALT A ALTERNATOR SYSTEM SET STEP 4CS STEP 5CS REFRESH RINSE SET TYPE MIN STEP 4CS Twin Alternating System Allows automatic alternation between t...

Страница 16: ...ntrol Valve for Separate Source Operation Select Separate Source Enabled for control operation For separate source opera tion the three wire connector is not used Selection requires that a connection...

Страница 17: ...fill flow control retainer assembly from the elbow Reinstall the elbow assembly and secure with the locking clip Disconnect the brine tube at the top of the salt keeper and force air into the brine tu...

Страница 18: ...ans former if inadequate voltage 4 Low battery after power outage D1 If power outage occurred and battery on board has low voltage the microprocessor may not recover cleanly and display properly Disco...

Страница 19: ...specification C Excessive water in brine tank C See problem 9 D Leaking faucets toilets etc D Repair or replace those items E Brine line flow control out of place E Replace Brine line flow control 7 L...

Страница 20: ...eter D Unplug meter from PC board if LED display lights appropriately replace meter E Defective PC board E Replace PC board 15 Control does not display correct A Power outage 2 years A Reset time of d...

Страница 21: ...SBV 8 Grid 1 104421 c 18X40 w 474 SBV 11 Grid 1 104423 d 24x50 w 474 SBV 6 Grid 1 104428 e 24x50 w 474 SBV 9 Grid 1 104423 f 18x40 w 474 SBV No Grid 1 104416 g 24x50 w 474 SBV No Grid 1 104426 h 30x50...

Страница 22: ...H125 PC Board 1 5 101746 Drive Gear 12x36 3 6 101459 Drive Gear Cover 1 Not Shown 103723 Optional Relay Kit PCM 1 Not Shown 103729 Optional Relay Kit 120V Pigtail Not Shown 101880 Auxiliary Switch Ki...

Страница 23: ...Plug 1 101825 Injector Assembly A Black 101826 Injector Assembly B Brown 101827 Injector Assembly C Violet 101828 Injector Assembly D Red 101829 Injector Assembly E White 5 101830 Injector Assembly F...

Страница 24: ...ystems 1 102322 H125 H150 Refill Port Plug Assy 1 2 101154 H125 H150 BLFC Adapter 1 3 101414 Locking Clip 1 4 102417 H125 H150 Refill Retainer Assy 1 4 8 103590 1 2 Refill Elbow Assy 1 5 102153 O Ring...

Страница 25: ...ine oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec tion Teflon tape is not necess...

Страница 26: ...ss Handle 2 7 109479 Bypass Rotor Seal Retainer 2 8 102159 O Ring 135 2 9 102161 O Ring 112 2 10 102160 O Ring 214 2 Bypass Valve Not Shown Bypass Vertical Adapter Assembly ORDER NO DESCRIPTION QTY 10...

Страница 27: ...with a hammer Do not use vaseline oils other hydrocarbon lubricants or spray silicone anywhere Teflon tape must be used on threads of the 1 NPT connection and on the threads for the drain line connec...

Страница 28: ...28 FLOW DIAGRAMS SERVICE AND BACKWASH FLOW DIAGRAMS RINSE AND FILL...

Страница 29: ...or disassemble the valve the wrench shown in various positions on the valve may be purchased to aid in assembly or disassembly Wrench part number is 102892 Loosens Drain Nut in Polytube Applications L...

Страница 30: ...n gallons capacity reaches 0 Time of regeneration will not be allowed to be set because of regeneration will always occur when gallons capacity reaches 0 DELAY IMMEDIATE oFF Reserve capacity not autom...

Страница 31: ...board The drive gear cover is held in place on the drive bracket by three clips The largest of the three clips is always orientated to the bottom of the drive bracket With the PC board facing up push...

Страница 32: ...force the spacer stack assembly in The control valve body bore interior can be lubricated with silicone to allow for easy insertion of the entire stack Do not use silicone or any other type of lubric...

Страница 33: ...urbine to remove it from the shaft Do not use a wire brush to clean the turbine Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar The turbine can be immersed in the che...

Страница 34: ...34 SERVICE RATES PRESSURE DROP CHARTS...

Страница 35: ...e Tank NO NO NO NO NO NO NO 3 8 3 8 3 8 3 8 3 8 3 8 3 8 2 2 2 2 4 2 4 2 5 3 7 5 7 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 D RED E WHITE G YELLOW H GREEN I ORANGE J LT BLUE K LT GREEN 0 22 0 27 0 46 0 46 0 56 0...

Страница 36: ...RANTY DOES NOT COVER defects caused by sand sediment or bacteria fouling accident fire flood Act of God misuse misap plication neglect alteration installation or operation contrary to Hellenbrand s pr...

Отзывы: