Solar sensor and divertor valve wires must be routed via the two cable entry holes at the back
of the Electromax Solar.
Cable glands and snap fit blanking plugs are supplied with the Electromax Solar. The cable
glands should be fitted into the cable entry holes selected for cable entry and secured in place
using the locknuts supplied.
The cable glands must be used to secure the electrical supply cables, the solar collector sensor
cable and the divertor valve cable (if fitted). Failure to do so can result in cables straining
internal electrical connections and lead to electrical failure. Failure due to inadequate cable
securing will not be covered by warranty.
The remaining holes not used should be blanked off using the snap fit blanking plugs
supplied.
Connection of all cables requires removal of top and front panels and removal of the control
panel rear cover. Refer to page 11 for panel removal.
3.8.1 240v 16A CONTROL PANEL AND BOOST IMMERSION HEATER CONNECTION
Connection of the control panel and boost immersion heater cable is made to the main terminal
block located behind the Electromax Solar control panel.
Use 3 core 1.5mm
•
2
flexible cable
Route the cable via one of the 20mm cable glands
•
Connect the Live (brown) conductor to terminal L2
•
Connect the Neutral (blue) conductor to terminal N2
•
Connect the Earth (green/yellow) one of the conductors marked
•
3.8.2 240v 16A IMMERSION HEATER CONNECTION
Connection of the immersion heater is made to the main terminal block located behind the
Electromax Solar control panel.
Use 3 core 1.5mm
•
2
flexible cable
Route the cable via one of the 20mm cable glands
•
Connect the Live (brown) conductor to terminal L1
•
Connect the Neutral (blue) conductor to terminal N1
•
Connect the Earth (green/yellow) one of the conductors marked
•
3.8.3 PROGRAMMABLE ROOM THERMOSTAT CONNECTION
Connection of the room thermostat cable is made to the main terminal block located behind
the Electromax Solar control panel.
Use 2 core 0.5mm
•
2
or 1.0mm
2
flexible cable suitable for 240v.
Route the cable via one of the 20mm cable glands
•
Connect room thermostat COM terminal B
•
Connect room thermostat N/O to terminal A
•
DO NOT connect to room thermostat N/C
•