059305-00 Rev. D
Heat-Timer Corp.
TMC Setpoin
t
TMC Trigger Delay
Selections:
40°F/4.5°C to 200°F/93°C
Default:
110°F/43°C
Available in Control Modes:
TMC or ETV + TMC
Menu Path:
/TMC Setpoint
If the Setpoint Input was set to EMS 4-20mA, the TMC Setpoint can only be changed remotely using the
4-20mA input signal. It will be available as read-only through the control (see “Setpoint Input” on page
38
).
A TMC Trigger Delay can be adjusted to help eliminate false alarms (see “TMC Trigger Delay” on page
).
WARNING
SCALD HAZARD! Water temperatures over 125°F (52°C) can instantly cause severe burns. Children, disabled,
and the elderly are at highest risk of being scalded. If anyone using hot water in the building fits the above
description, or if local codes or state laws require specific water temperatures at the outlet, it is
recommended to not exceed at Setpoint limit of 125°F (52°C). Water drained from system drain valves may
also be extremely hot. Make sure all connections are tight and direct all water flow away from personnel.
Default:
15 sec
Selections:
0 to 60 seconds
Available in Control Modes:
TMC or ETV + TMC
Menu Path:
/TMC Setpoint > TMC Trigger Delay
Description:
The TMC Trigger Delay prevents the alarm from being triggered immediately and the TMC valve from
closing unless the alarm situation is maintained for the full delay period. This helps eliminate false alarm
situations that normally may only last for a few seconds.
ETV Platinum Plus Display and Programming 45
Description:
The TMC Setpoint is the mixed valve outlet temperature above which the ETV Platinum Plus will close the
TMC valve and trigger an alarm. This action prevents the mixed outlet from reaching excessive
temperatures. An alarm message is displayed (see “Alarm Messages” on page
35
) and the event will be recorded in the Alarm Log (see “Alarm Log” on page
50
).
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...