34 ETV Platinum Plus Installation and Operation Manual
059305-00 Rev. D
Heat-Timer Corp.
Default Display
The ETV Platinum Plus default display varies depending on selected Control Mode and alarm
condition.
NOTE:
When in the ETV + TMC mode, the area above the variable function buttons that describe the button’s
function may not be displayed due to inactivity. Pressing the far-right button in the default display will enter
into the Menu screen.
Display Icons and Message
s
The following icons and messages may be displayed by the ETV Platinum Plus.
ETV Mode
TMC Mode
ETV + TMC Mode
#
Mode
Message
Description
1 All
The battery icon blinks when the battery is weak.
2 TMC
TMC Limit = 160°F
Valve Close! See
Log
The alarm is set to be triggered when the system temperature
exceeds the displayed setting for the specified Delay Alarm period.
45
.
The system temperature exceeded the alarm limit. TMC lockout
has occurred (the control closed the TMC valve). View the alarm
50
).
When in the ETV + TMC mode, this message will alternate with
the “TMC Limit = 160°F” message.
3 TMC
Valve Open
The system temperature is below the alarm limit (TMC Alarm is
not triggered). The control opened the TMC valve.
4 ETV
No Flow!
The Flow Switch option is enabled and no flow is detected. See
“Wiring the Flow Prove” on page
27
.
5 TMC
TMC Lockout
Alarm
When a TMC Lockout occurs, “TMC Lockout” blinks.
When an active alarm occurs, “Alarm” blinks.
6 All
Target Temperature
EMS Open/Short
The control target temperature setting.
When EMS is used and the signal fails, “EMS Open/Short” is shown.
7 All
Value or Switch Icon When Aux 1 is configured as Temperature input, the value is shown.
When Aux 1 is configured as Switch, the switch status icon is shown.
8 All
Value or Switch Icon When Aux 2 is configured as Temperature input, the value is shown.
When Aux 2 is configured as Switch, the switch status icon is shown.
9 All
Communication
Lost!
Internet Communication (ICMS) option only.
The control is set to communicate over a network and communication
is not detected. This message will alternate with the date and time
message.
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...