059305-00 Rev. D
Heat-Timer Corp.
BACnet Communications Wiring
To connect the ETV Platinum Plus to a BACnet interface:
1. Run a CAT5 cable through a knockout located on the bottom of the ETV Platinum Plus
enclosure.
2. Connect the CAT5 cable to the Ethernet connector on the ETV Platinum Plus module.
3. Run the BACnet connection wires through a knockout located on the bottom of the
ETV Platinum Plus enclosure.
4. Connect the positive (+) wire to terminal 30 on the ETV Platinum Plus module.
5. Connect the ground wire to terminal 31 on the ETV Platinum Plus module.
BMS - BACnet
Connect the negative (–) wire to terminal 32 on the ETV Platinum Plus module.
ModBUS Communications Wiring
To connect the ETV Platinum Plus to a ModBUS interface:
1. Run the ModBUS connection wires through a knockout located on the bottom of the
ETV Platinum Plus enclosure.
2. Connect the positive (+) wire to terminal 30 on the ETV Platinum Plus
module.
3. Connect the ground wire to terminal 31 on the ETV Platinum Plus module.
4. Connect the negative (–) wire to terminal 32 on the ETV Platinum Plus module.
Completing the Wiring
1. After all wiring to the ETV Platinum Plus is complete, apply power to the ETV Platinum Plus and
all Actuators.
2. Do not re-install the Enclosure wire cover at this point as access to the PROGRAM / RUN switch is needed
for programing of the module.
28 ETV Platinum Plus Installation and Operation Manual
6.
BMS - ModBUS
+ G
-
CAT5
+ G
-
3
.
With power supplied to the ETV Platinum Plus, the power loss capacitor of the actuator
if applicable
requires about 2
minutes to fully charge.
Figure 1
3
: Location of the Actuator Dip Switches and Capacitor Jumper
Содержание ETV Platinum Plus
Страница 9: ...ETV Platinum Plus Stainless Steel Valve Dimensional Specifications 9 059305 00 Rev D Heat Timer Corp...
Страница 31: ...Piping Diagrams 31 059305 00 Rev D Heat Timer Corp Figure 14B Two Mixing Valves and a TMC Safety Valve...
Страница 54: ...059305 00 Rev D Heat Timer Corp Notes 54 ETV Platinum Plus Installation and Operation Manual...
Страница 55: ...059305 00 Rev D Heat Timer Corp Notes ETV Platinum Plus Installation and Operation Manual 55...