HB-TP180/200
Checking Facility for Temperature Control Units
Testing
O8354-EN 2018-11
41
Fig. 21: External Temperature table
16.
Open the shut-off valve (move the lever upward).
17.
Only for units with additional equipment ZE and external
Pt
100 sensor: Connect the “Pt 100 test adapter” to the
connection
ZE
at the unit and enter the following measured
values in “M temperature (B)”.
External
(Displayed on unit)
Fig. 22: Table external pressure
18.
Open the
Nominal values
menu page.
19.
Set the
Nominal value 1
parameter to 40 °C.
20.
When the nominal value 40 °C is reached, switch off the unit
by pressing the
key and enter the following measured
valu
es in “Pressure measurement”:
Pressure return line (HB-TP180/200)
System pressure actual value
(Displayed on unit)
Pressure gauge (rear of unit)
only for ZU (Thermo-5): Pressure main line (HB-TP180/200)
21.
Carry out safety test (
page 42).