HB-TP180/200
Checking Facility for Temperature Control Units
Testing
O8354-EN 2018-11
35
7.2.4 Settings
Testing temperatures
Fig. 11: Additional test temperatures
If additional testing temperatures must be run, this can be
conducted using
Testing temperature 3
,
Testing temperature 4
.
Proceed as follows in order to set the testing temperatures:
1.
Open the
Service \ TP-test
menu page.
2.
Set
Testing temperature 3
,
Testing temperature 4
parameter
to the desired figure.
NOTICE!
The predefined Testing temperatures 1 and 2
cannot be changed.
Testing temperature 1
is set to 40 °C (Test step 4)
and
Test temperature 2
is set to maximum
temperature (Test step 3).
NOTICE!
By default,
Testing temperature 3
and
Test
temperature 4
are set to "OFF". The test
temperatures are not run when the "OFF" setting is
activated.
Tolerances
Fig. 12: Setting tolerances
Proceed as follows in order to set the tolerances:
1.
Open the
Service \ TP test
menu page.
2.
Set the desired figures for the following parameters:
Flow measurement tolerance
Pressure measurement tolerance
Temp. measurement int. tolerance
Temp. measurement ext. tolerance
Temp. diff. Tol. Main-/Return line
Pump pressure tolerance
Gauge pressure tolerance
NOTICE!
By default, the tolerances are adjusted according to
the recommendations of HB-Therm.