5.4.
External Relay Speed Control Wiring (For remote selection of pump speed)
Note: For third party controls and Hayward controls that are NOT software compatible.
Figure 5.4-1
Connection wire must be rated for a minimum of 300V. See section 6.6.
Error! Reference source not
found.
for more details. Do
not
connect to the lower “COMBUS” or wall mount “DISPLAY” data
terminals.
The LifeStar® VS pump can also be controlled from third party control using relay contacts to select the
speeds set in the Timer Menu (see section 6.7). In addition to this section you may also consult the third
party control installation manual for electrical connection details. Once installed, Remote Control Mode
must be set to Relay Control in the pump Configuration Menu (see section 6.6). Preset Speeds 1-4 and
Quick Clean are disabled when the pump is remotely controlled. When Inputs 1-3 are activated via the
control relays, timer speeds 1-8 are selected according to the following table:
Timer
Speed
INP1
Status
INP2
Status
INP3
Status
1
OFF
OFF
OFF
2
ON
OFF
OFF
3
OFF
ON
OFF
4
ON
ON
OFF
5
OFF
OFF
ON
6
ON
OFF
ON
7
OFF
ON
ON
8
ON
ON
ON
The number of speeds available depends on the number of auxiliary relays used as noted below:
1.
Filter pump relay plus 1 auxiliary relays allows control of 2 speeds
2.
Filter pump relay plus 2 auxiliary relays allows control of 4 speeds
3.
Filter pump relay plus 3 auxiliary relays allows control of 8 speeds