Chapter 2 System Installation with the Content-
Server 4000 Series
© 2017 Harmonic Inc. All rights reserved.
65
Harmonic MediaGrid Release 4.1
Connecting the Harmonic MediaGrid 4000 System Components
Figure 2–25: Network Switches and Client Network Connections
Connecting Components in Rack One
1. Connect CX4 cables to the two 10 GbE ports on the back of rack one’s first switch. Connect
the other end of the cables to available 10GbE ports on rack two’s switch that connects to the
client network.
2. Connect CX4 cables to the two 10 GbE ports on the back of rack one’s second switch.
Connect the other end of the cables to available 10 GbE ports on rack one’s switch that
connects to the client network.
3. Connect the top network switch to the client network.
Connecting Components in Rack Two
1. Connect CX4 cables to the two 10GbE ports on the back of rack two’s first switch. Connect
the other end of the cables to available 10GbE ports on rack two’s switch that connects to the
client network.
2. Connect CX4 cables to the two 10 GbE ports on the back of rack two’s second switch.
Connect the other end of the cables to available 10 GbE ports on the back of rack one’s
switch that connects to the client network.
3. Connect the top network switch to the client network.
4. Continue with
Connecting the Power Cables in a System with ContentServer 4000 Series
to complete
the hardware installation.
Connecting the Power Cables in a System with ContentServer 4000 Series
With all of the network cable connections completed, connect the power cables as detailed in the
following order.
IMPORTANT:
Do not turn on any equipment yet.
Chapter 4, System Configuration
includes instructions for
powering on each Harmonic MediaGrid device.
1. The ContentServer and ContentStore 4000 series have power buttons on the front panel. The
ContentStore 5840 has power switches on the rear panel. Ensure that all power switches are
off.
Do not
plug the cords into power sources yet. To take advantage of the redundant power
supplies, ensure that separate, isolated power sources are available for each PSU.
10GbE Switch
To Client Network
10GbE Switch
To Client Network
First Switch
Second Switch
First Switch
Second Switch
Rack Two
Rack One