Attention!
If local regulations require the installation of a residual current operated protective device, the following applies:
In case of a fault the drive controller is able to generate d.c. leak currents without zero crossing. Drive controllers
there fore must only be operated with RCDs
1
) type B for a.c. fault currents, pulsating or smooth d.c. fault currents,
which are suitable for servo controller operation, see IEC 60755. RCMs
2
) can additionally be used for monitoring
purposes.
1)
Residual current protective device
2)
Residual current monitor
Note the following points:
• Switching the mains power:
– In case of too frequent switching the unit protects itself by high-resistance isolation from the system. After a
rest phase of a few minutes the device is ready to start once again.
• TN and TT network: Operation is permitted if:
– in the case of single-phase devices for 1 x 230 V AC the supply system conforms to the maximum overvoltage
category III as per EN 61800-5-1.
– In the case of three-phase devices with external conductor voltages 3 x 230 V AC, 3 x 400 V AC, 3 x 460 V AC and 3 x
480 V AC
1. the neutral point of the supply system
is grounded
and
2. the supply system conforms to the maximum overvoltage category III as per EN 61800-5-1 at a system
voltage (external conductor neutral point) of maximum 277 V.
• IT network: not permitted!
– In case of a ground fault the electrical stress is approximately twice as high. Clearances and creepages to EN
61800-5-1 are no longer maintained.
• Connection of the drive controllers by way of a line reactor is mandatory:
– where the drive controller is used in applications with disturbance variables corresponding to environment class
3, as per EN 61000-2-4 and above (hostile industrial environment);
– in the case of single-phase mains supply;
– for compliance with EN 61800-3 or IEC 61800-3.
• For further information on permissible current loads, technical data and ambient conditions please refer to the
appendix.
Note:
Please be aware that the YukonDrive® is not rated for environment class 3. Further measures are essential in order for
that environment class to be attained! For further information please consult your project engineer.
Table 24.1 Connected load and mains fuse
YukonDrive®
Device connected load
1)
[kVA]
Max. line crosssection
2)
of term.
[mm²]
Specified mains
fuse. duty class gG [A]
With line reactor
(4 % u
)
Without line reactor
-1021
1.3
1.6
2.5
3 x max. 16
-1022
1.5
1.9
2.5
3 x max. 6
-1031
2.6
3.2
2.5
3 x max. 16
-1032
2.7
3.3
2.5
3 x max. 10
-1041
3.5
4.3
4
3 x max. 20
-1042
5.0
6.1
4
3 x max. 16
1)
At 3 x 230 V AC or 3 x 400 V AC mains voltage
2)
The minimum cross-section of the mains power cable depends on the local regulations and conditions, as well as on the rated current
of the drive controller.