40
1003370 05/2016 V01
D1
D2
Action
Reaction
Explanation
“STO” and power stage
“ENPO” enabled
Ready for start
Power stage ready
Attention!
Make sure before the next step, “Start enable”, to preset a plausible setpoint value, because the presetting ist trans-
ferred directly to the drive when motor control starts.
“Start” enabled
ON
Drive powered, control active
Table 40.1 Display D1/D2 during motor activation
Display readout after drive start-up
For details on optimizing the drive in your application refer to the DriveManager 5 Online Help and the Operating
Manual YukonDrive®.
4.3 Serial commissioning
An existing parameter data set can be transferred to other YukonDrive® controllers using DriveManager 5. For details
refer to the DriveManager 5 Online Help.
4.4 Integrated operator control unit
The built-in operator control unit permits diagnosis of the YukonDrive®. The operator control unit comprises the fol-
lowing elements, all located on the front of the device:
• 2-digit 7-segment display (D1, D2)
• 2 pushbuttons (T1, T2)
The following functions and displays are available:
• Display of device state (see section 5.1 , “Device states”, on page 42) The device state is displayed after switching on
the control supply. If no input is made via the keypad for 60 seconds, the display switches back to the device state.
• Display of device error state (see page 42) If a device error occurs the display immediately switches to show the
error code.
• Parameter setting (display “PA”) (see section 4.4.3 )
Resetting device parameters to their factory setting
• Ethernet IP address setting (display “IP”) (see section 4.4.4)
Setting of the Ethernet IP address and the subnet mask
• Field bus settings (display “Fb”) (see section 4.4.5 )
Setting of field bus address for example
Illustration 40.2 Integrated operator control unit YukonDrive®
D1
D2
T2
T1