Detail 3: Mains filter and mains connection
At the output of the mains filter and at the AC mains con-
nection (X3):
• Connect the wire strands at the output of the mains
filter directly to the AC mains connection (X3) of the
YukonDrive®. The strands must not be extended, so the
mains filter should be installed correspondingly close to
the YukonDrive®. But be sure to maintain the necessary
minimum clearance (see table 2 on page 6).
• Fix the strands to the shield connection plate using a
cable tie as necessary.
• The leakage current of the YukonDrive® is >3.5 mA. So:
– Connect the protective conductor from the output of
the mains filter to the connection (X3) of the Yukon-
Drive®
and
– one of the PE connections on the heat sink of the Yu-
konDrive® via a cable of at least the same cross-section
to the main ground of the distributor rail.
Detail 4: Control cables
At the control terminals (X4) of the YukonDrive® note the
following points:
• Strip the shielding of the control cables back only as
short as absolutely necessary.
• Connect the control cable shields across a wide area to
the shield connection tab of the mains filter by the clamp
supplied. If this is not possible, lay the control cable
shielding directly across a wide area on the backing plate
directly adjacent to the YukonDrive®.
Illustration 18.1 Specimen setup - Detail 3:
mains filter and mains connection
Illustration 18.2 Specimen setup - Detail 4: Control cables
X3
X4