3.4 Effective EMC installation
3.4.1 Interference immunity of drive controllers
Attention!
This is a restricted availability product in accordance with IEC 61800-3. This product may cause radio interference in
domestic environments; in such cases the operator may need to take appropriate countermeasures. External radio
frequency interference (RFI) suppression filters (EMCxxx) are available for the drive controllers. With the measure-
ment method specified and the external mains filter, these drive controllers conform to the EMC product standard
IEC 61800-3 for “First environment” (residential C2) and “Second environment” (industrial C3).
3.4.2 Specimen setup
The specimen setup presented on the following pages is intended to illustrate the key measures necessary to ensure
EMC-compatible setup.
Note:
The specimen setup merely presents a recommendation, and does not automatically guarantee compliance with ap-
plicable EMC directives. The installer/operator of a machine and/or item of plant must provide proof of compliance
with the protection targets stipulated in the standard.
Overview
Illustration 16.1 presents an overview of the minimum components required:
A. Backing plate with cable ducts
B. YukonDrive®
C. Mains filter
D. Line reactor
E. Distributor rail for AC power supply and control supply (+24 V DC)
The layout and cabling are based on the instructions set out in section 3.1, „Notes for installation“, on page 9. The numbe-
red red arrows refer to four very important detailed notices presented on the following pages.