Illuminator User Manual  

Page 18 

Two simple setup configurations will be described to illustrate common lighting scenarios. 
 

Setup 1: 

Two independent scenarios 

  Athletics Oval where all lights come on together. Combined power of all lights is 12 kW 

  Soccer Oval where all lights come on together. Combined power of all lights is 16 kW 

 

Only two out of eight Illuminator controls are needed in this example. Let’s assume that 
Illuminator Control 1 is driving the contactor that turns on Athletic Oval lights, and that 
Illuminator Control 2 is driving the contactor that turns on Soccer Oval lights 
This information is entered as follows: 
 

 

 

Setup 2: 

Two scenarios that share one or more common Illuminator controls 

  Soccer 50 lux where half of the lights come on. The power of this portion of the lights is 9 

kW 

  Soccer 100 lux where all of the lights come on. The power of the additional half of the 

lights is 11 kW,  for a total of 20kW 
 

Only two out of eight Illuminator controls are needed in this example. Let’s assume that 
Illuminator Control 1 is driving the contactor that turns on the first half of the lights, and that 
Illuminator Control 2 is driving the contactor that turns on the second half of the lights. 
This information is entered as follows: 
 

 

 
 
You can exit at any time without making changes by clicking the “Cancel” button. 
Save the new values by clicking on the “Save” button. 
 
 
 

Содержание Illuminator

Страница 1: ...HALYTECH Illuminator User Manual Page 1 Illuminator Floodlight Control and Facility Monitoring System USER MANUAL Illuminator User Manual Version 3 21 Copyright Halytech All rights reserved...

Страница 2: ...images photographs animations video audio and music are owned by Halytech You may not reverse engineer decompile or disassemble this software for any purpose No part of this software may be copied re...

Страница 3: ...Setup Mode 25 Normal Operation 26 Communicating with a PC 26 Lights 26 Clubs 28 Report 29 Advanced Operation 31 Automatic Daily E mail Reports 31 Inputs 32 Calibrating Counter Inputs if present 33 Sc...

Страница 4: ...s 3 Generating up to eight 8 alarms 4 Receiving SMS commands 5 Sending SMS messages 6 Logging status control and alarm activity 7 Being configured by the user through any standard web browser 8 Sendin...

Страница 5: ...lights Each light scenario can have its own separate period The administrator can allow up to 49 normal users to control the lights Each user is given a different 4 digit PIN and the authority to con...

Страница 6: ...delay in seconds can be set if desired It is used to eliminate large current draws that can occur when multiple controls turn on at exactly the same time With the Turn on delay set to x seconds the co...

Страница 7: ...or an inactive or OFF state The active state is indicated by shorting the two terminals together while the inactive state is indicated by the terminals staying open A switch state must be stable for...

Страница 8: ...ding to the next number After the 3rd attempt to the 3rd number if applicable the unit will stop sending SMS and wait indefinitely for the alarm to be reset This limits the number of SMS transmissions...

Страница 9: ...can use any computer regardless of type and operating system to connect to an Illuminator NO SPECIAL SOFTWARE is required The web server is used for 1 Setting up an Illuminator for the first time 2 Se...

Страница 10: ...or does not have an ON OFF switch The unit starts operating as soon as power is applied The unit is fitted with two power connectors Charger for connection of an external mains power supply Battery fo...

Страница 11: ...240V circuits They provide a suitable contact rating for driving the floodlight contactors The Illuminator provides voltage free relay contacts Consequently you will also need a separate power supply...

Страница 12: ...etup is configured for driving 4 contactors hence there are 4 isolation relays Your electrician will be able supply the isolation relays as a part of the Illuminator installation Inputs Advanced Use O...

Страница 13: ...nt loop sensors require an external 120 Ohm W resistor ii Voltage inputs may require up to two external resistors SENSOR RANGE VALUE OF Rx VALUE OF Ry 0 2 5V None required Leave out 0 5V 1 Kohm W meta...

Страница 14: ...Area Network LAN connector is used for connections to a PC or to a LAN AUX1 connector is not used in a standard Illuminator It is reserved for future enhancements and special applications The optiona...

Страница 15: ...factory The DB9 connector plugs into Illuminator AUX2 connector The Illuminator provides all power and communications signals to the keypad The other end of the cable is attached to the numeric keypad...

Страница 16: ...minator date and time 3 Setting your username and password 4 Setting network and e mail settings Setting up clubs their PINs and access rights is covered in the section Normal Operation Connect locall...

Страница 17: ...For normal users this works in conjunction with the periods during the day in which they are allowed to control lights Turn off delay minutes is useful for classic non LED lights If a user commands th...

Страница 18: ...al lights This information is entered as follows Setup 2 Two scenarios that share one or more common Illuminator controls Soccer 50 lux where half of the lights come on The power of this portion of th...

Страница 19: ...Set from computer to synchronise the date and time with that of your computer Next select the Timezone appropriate to your location Any applicable Daylight saving time adjustments will be made automa...

Страница 20: ...are user and changeme respectively It is strongly advised that these be changed as soon as possible to prevent unauthorised access In the event that you forget your new user name or password you will...

Страница 21: ...for more information about initial connection of an Illuminator to a Local Area Network LAN To set up Network parameters access the Change Setup page as described in Setting up an Illuminator for the...

Страница 22: ...IM card GPRS Access Point Name APN is provided by the mobile phone company which supplied your SIM card At the time this manual was issued the correct settings for common Australian networks were Tels...

Страница 23: ...optusnet com au Vodafone SMTP mail server smtp vodafone net au From email address In the process of sending an e mail the Illuminator must identify itself to the mail host computer with a valid e mail...

Страница 24: ...ed only if there is no reply from the Primary DNS From e mail address In the process of sending an e mail the Illuminator must identify itself to the mail host computer with a valid e mail address Set...

Страница 25: ...name of a file which will hold your settings Load Setup from Disk Once you have saved system settings as described above you can upload them to any other Illuminator To load the settings click on the...

Страница 26: ...ly to the Illuminator as described in Appendix A A successful log on will automatically display the Lights screen Lights This screen shows the current state of all light scenarios their operating mode...

Страница 27: ...l bring up a new window To set On and Off times for the scenario on a particular day of the week simply enter the desired On and Off times in the appropriate row To select the Operation mode for the s...

Страница 28: ...by clicking Cancel Let s add a new user in position 4 Abbreviation LSOC Club Name Ladies Soccer Club PIN 1119 Authorised to control scenarios 3 and 4 Click on Change in row 4 Using the details above...

Страница 29: ...being transferred you can specify the date and the time of the first record and the number of days the report should span The report is an Excel compatible file If you have Excel installed on your com...

Страница 30: ...ced Operation Automatic Daily E mail Reports for details It is possible to connect an Illuminator to electricity meters to measure exactly how much electricity is used by lights at each field Once thi...

Страница 31: ...n logged A non zero setting will cause e mail report to be sent only if the floodlights have been used in the previous day However even if there is no significant data logged a report will be sent whe...

Страница 32: ...want to monitor a meter that is not associated with any specific lighting circuit then you must use and input that has no corresponding light control For example you may want to monitor only 3 Inputs...

Страница 33: ...nter inputs connected to water and or electricity meters It allows you to obtain a cost in dollars by multiplying litres or kWh reading by their cost When set to a non zero value it does the conversio...

Страница 34: ...12 Click on Save to save the calibration You will need to perform the calibration procedure for all inputs connected to electricity meters You can exit at any time without making changes by clicking t...

Страница 35: ...nt and then use a light meter to get the actual reading of ambient light for the second point You can exit at any time without making changes by clicking the Cancel link Save the new values by clickin...

Страница 36: ...inator input meter monitoring electricity for control 1 must be connected to input 1 meter monitoring electricity for control 2 must be connected to input 2 etc 2 Set up Illuminator status inputs with...

Страница 37: ...SMS text I am being vandalised SMS Sending enabled If not already displayed access the Change Setup page as described in Setting up an Illuminator or the first time earlier in this document Click on...

Страница 38: ...ms provide additional information about the progress of the alarm sequence by displaying a numerical code Please refer to section SMS Alarms for the key to the code Resetting Alarms Active alarms can...

Страница 39: ...g in the form Data is downloaded backwards in time In other words the most recent records are downloaded first In order to minimise the amount of data being transferred you can specify the date and th...

Страница 40: ...n or that the cellular phone module inside the Illuminator is not responding Is the antenna plugged in It is a normal indication during power up and immediately following remote access It typically la...

Страница 41: ...commands that cannot be executed by the Illuminator will initiate a response SMS describing the reason why the command could not be executed Each SMS response is prefaced by Location SMS Responses are...

Страница 42: ...combination of both 2 There must be only one space between the words of a command 3 SMS commands will be ignored while in the Remote Access mode Therefore if an SMS command is not acknowledged by a r...

Страница 43: ...er 8 Illuminator is attempting to send 2nd SMS to 3rd phone number 9 Illuminator is attempting to send 3rd SMS to 3rd phone number 10 Illuminator has made a maximum of 9 SMS send attempts without rece...

Страница 44: ...sequence The red light turns on Users have up to 30 s to input the next key Failing to do it clears the keypad turning the red light off Each keypress is acknowledged with a short beep The keypad will...

Страница 45: ...0 seconds 5 Start an Internet browser program such as Microsoft Internet Explorer or Google Chrome on your PC 6 Type 192 168 0 188 as the web address and press the return or enter key 7 The Illuminato...

Страница 46: ...es Communications Network Connections 2 If in the newly opened window you don t have an item called Network Bridge go to step 3 If you do right click on it and select Properties Go to step 4 3 Right c...

Страница 47: ...the change mode with a long press and then change digits in the same manner as described in step 4 above 8 After the last digit is entered the display will again show the message in step 6 Briefly pre...

Страница 48: ...command to the Illuminator pppp GPRS n yourEmailAddress where pppp 4 digit PIN of the 1st user the Administrator n number of minutes the system will wait on line for you 10 is a good choice yourEmail...

Страница 49: ...and for each light deactivation So for example if you have 3 fields used by one lot of users 5 days a week the number of SMS will be 3 x 2 x 1 x 5 30 per week or approximately 130 SMS per month An SMS...

Страница 50: ...far as it will go it only moves a couple of mm UNLOCKED POSITION LOCKED WORKING POSITION 4 Replace the access cover To remove the SIM card 1 Remove the modem access cover as previously described 2 Us...

Страница 51: ...ll required Network E mail parameters ensure that it is connected to the appropriate network as selected by the E mail sending method Repeatedly and briefly press the keypad key until the display show...

Страница 52: ...ring detected 0 ST 0 7 Numeric value of analogue status Analogue status log record 50 2 ST STATE 50 65 STx y Digital status change 100 2 CNT STATE 100 107 SCNx y Scenario change 200 AL 200 207 Alarm x...

Страница 53: ...t Table decode ST input number 0 7 STATE digital status state 0 OFF 1 ON CNT control number 0 3 AL alarm number 0 7 x alarm number 1 8 equals AL 1 SEQ alarm sequence step 0 10 y alarm sequence number...

Отзывы: