DC bus over/under voltage protection
Bus voltage>overvoltage shutdown value: the compressor stops, then switches into the bus overvoltage protection.
Bus voltage<overvoltage recovery value, cancel the bus overvoltage protection.
Bus voltage<under voltage shutdown value: the compressor stops, then switches into the bus under voltage
protection.
Bus voltage<voltage recovery value, cancel the bus under voltage protection.
AC input over/under voltage protection
Drive comes with AC voltage detection, when input voltage is too low, the input current will be too high, damage can
occur
Input voltage<under voltage shutdown value, the compressor stops, then switches into the input under voltage
protection.
Input voltage>voltage recovery value, cancel the under voltage protection.
Drive comes with AC voltage detection, if the input voltage is too high, damage can occur.
Input voltage>over-voltage shutdown value, the compressor stops, then switches into the input overvoltage
protection.
Input voltage<over-voltage recovery value, cancel input over-voltage protection.
Communication error:
Drive priority detects the model code after power is on for 30 seconds .
Compressor type
Model Code
TNB220FFEMC
0x02DC
TNB306FFEMC
0x02DD
If the model code is not within the model range or or the correct data is not received within the 30 seconds, the unit
will go into a communications failure mode and will shut down.
When the correct data is within the model code range the error will be canceled.
Note: For debug mode, when the model code is not within the range of models, sentenced to communication
failure; when the model code within the model range, then cancel the error
PFC switch value:
When PFC sampling current>PFC open switch current and the DC bus average voltage<PFC open switch voltage,
then opening PFC;
When PFC sampling current<PFC off switch current, off PFC.
Protection value
Compressor type TNB220FFEMC:
No.
Error Description
Device
Protection
Value
1
Compressor phase current Limit frequency protection shutdown current value (RMS)
18A
2
Compressor phase current Limit frequency protection decrease frequency current value (RMS)
13A
3
Compressor phase current Limit frequency protection recovery current value (RMS)
10A
4
PIMTemperature shutdown protection
105°C
5
Drive input current limit frequency protection shutdown current value (RMS)
23A
6
Drive input current limit frequency protection decrease frequency current value (RMS)
18A
7
Drive input current limit frequency protection recovery current value (RMS)
13A
8
AC input overvoltage shutdown value
280V
9
AC input overvoltage recovery value
265V
10
AC input under voltage shutdown value
155V
11
AC input under voltage recovery value
185V
12
DC bus overvoltage shutdown value
390V
13
DC bus overvoltage recovery value
380V
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...