PIM temperature protection:
Temperature more than 105°C, and continue 5 seconds, then drive shutdown protection.
Compressor startup failure protection:
The drive will attempt to start the compressor 5 times, at intervals of 15 seconds. When the drive is making five
times the driving signal cannot normally drive the compressor, for the protection of the relevant parts, compressor
will immediately shut down, and the drive will have the compressor drive failure protection.
Limit frequency/shutdown protection
Compressor current protection:
Error
Protection
Protection Condition
Result Symbol
Shutdown
protection
Compressor phase current> compressor phase current shutdown
protection current (RMS) , the compressor immediately stop, drive into the
limitedfrequency overcurrent protection.
Limit
frequency
protection
Compressor phase current>compressor Phase current Limit frequency
protection current (RMS) , the compressor will decrease the frequency by
the 2Hz/sec rate.
Limit frequency
protection
After compressor decrease the frequency, compressor phase current
limit frequency protection current (RMS) ≥compressor phase current>
compressor phase current protection recovery current (RMS) , forbid
increase the compressor frequency.
Forbid increase
the compressor
frequency
Protection
recovery
Compressor phase current≤Compressor phase current protection recovery
current (RMS) , cancel the compressor limit frequency protection and
normally operation.
Input current protection of driver:
Error Protection
Protection Condition
Result Symbol
Shutdown
protection
Compressor phase current>compressor phase current shutdown
protection current (RMS) , the compressor immediately stop, drive into the
limitedfrequency overcurrent protection.
Limit frequency
protection
Compressor phase current>compressor Phase current limit frequency
protection current (RMS) , the compressor will decrease the frequency by
the 2Hz/sec rate.
Limit frequency
protection
After compressor decrease the frequency, compressor phase current
limit frequency protection current (RMS) ≥compressor phase current>
compressor phase current protection recovery current (RMS) , forbid
increase the compressor frequency.
forbid increase
the compressor
frequency
Protection
recovery
Compressor phase current≤Compressor phase current protection recovery
current (RMS) , cancel the compressor limit frequency protection and
normally operation
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...