82
FlexFit Pro
DC bus over/under voltage protection:
Bus voltage>overvoltage shutdown value, the compressor stop, then drive into the bus overvoltage protection.
Bus voltage<overvoltage recovery value, cancel the bus overvoltage protection.
Bus voltage<under voltage shutdown value, the compressor stop, then drive into the bus under voltage protection.
Bus voltage>voltage recovery value, cancel the bus under voltage protection.
AC input over/under voltage protection:
Drive come with AC voltage detection, avoid the input voltage is too low, cause the input current is too high,
damage the device.
Input voltage<under voltage shutdown value, the compressor stop, then drive into the input under voltage
protection.
Input voltage>voltage recovery value, cancel the under voltage protection.
Drive come with AC voltage detection, avoid the input voltage is too high, damage the device.
Input voltage>overvoltage shutdown value, the compressor stop, then drive into the input overvoltage protection.
Input voltage<overvoltage recovery value, cancel input overvoltage protection.
Communication error:
Drive priority detect the model code after power on .the 30s after power on is the time for the model code setting.
And need to complete the model code setting within this 30s, if setting completely, are not allowed to change.
Compressor type
Model code
MNB42FDAMC
0x03DE
If model code is our of model range or no right communication data is received within 30s, communication failure is
confirmed, execute stop protection under communication failure, in the meanwhile, relevant error code is sent back.
When communication is confirmed, if right data is received again and within normal range, error is removed.
Remarks: for debugging mode, when model code is not within model range, communication error is confirmed,
when model code is within model range, error is removed.
PFC switch value
When PFC sampling current>PFC open switch current and the DC bus average voltage<PFC open switch voltage,
then opening PFC;
When PFC sampling current<PFC off switch current, off PFC.
Protection value
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...