70
FlexFit Pro
4. Error Code
4.1 Failure code indoor unit
AL24LP2VHA AL36LP2VHA AL48LP2VHA
LED flash times of
indoor PCB
LR.Recever
digital display
Contents of malfunction
Possible reasons
LED4
LED1
0
1
01
Malfunction of indoor unit ambient
temperature sensor
Sensor disconnected, broken, shorted,
or at wrong position.
0
2
02
Malfunction of indoor unit piping
temperature sensor
Sensor disconnected, broken, shorted,
or at wrong position.
0
4
04
PCB EEPROM error
EEPROM chip disconnected, broken,
or programmed incorrectly.
PCB defective.
0
7
07
Abnormal communication between
indoor and outdoor units
Poor wiring connections, faulty wiring,
poor power supply, incorrect addressing
of indoor units, malfunction of slave unit
programming in MAXI system; faulty
PCB.
0
8
08
Abnormal communication between
wired controller (or IR reciever) and
indoor unit
Wrong connection or wired controller
broken, or PCB faulty
0
12
0C
Malfunction of drain system
Condensate pump disconnected
or faulty, float switch a wrong
position, disconnected or faulty, or a
disconnection of the short circuit bridge
0
13
0D
Zero cross sigal wrong
Zero cross signal not detected
0
14
0E
Indoor unit DC fan motor abnormal
Fan motor disconnected, faulty wiring,
motor failure, or faulty circuit to motor
Note:
1. The outdoor failure can also be indicated by the indoor unit, the checking method as follows: If the outdoorerror
code is M (DECIMAL) , the indoor unit's I.R. receiver display will show the after converted hexadecimal code of
"M+20" (DECIMAL) , for example, if the outdoor error code is 2, the indoor unit I.R. receiver display will flash the
error code 16 (2→2+20=22→change deciaml 22 to hexadecimal code, get 16)
2. LED4 is a red one on the indoor PCB, LED1 is a yellow one.
3. To get much more details about the out door unit failure, please refer to the outdoor unit trouble shooting list.
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...