79
FlexFit Pro
No.
Error Description
Device
Protection
Value
14
DC bus under voltage shutdown value
180V
15
DC bus under voltage recovery value
200V
16
Communication shutdown protection time
30S
17
PFC open switch current (RMS)
8A
18
PFC open switch voltage
360V
19
PFC off switch current (RMS)
5A
Compressor type TNB306FFEMC:
No.
Error Description
Device
Protection
Value
1
Compressor phase current Limit frequency protection shutdown current value (RMS)
23A
2
Compressor phase current Limit frequency protection decrease frequency current value
(RMS)
18A
3
Compressor phase current Limit frequency protection recovery current value (RMS)
14A
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...