background image

ESPRIT Gas Extinguishing User Manual 

 

CONFIGURING THE PANEL 

 

 
 

 

79 

Approved Document Ref: UI-ESG-01 Issue 2.0 

Report Menu Breakdown 

 

 

 

 

 

 

 

 

 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ESG-2001

Страница 1: ...NSTALLATION COMMISSIONING OPERATING MANUAL This manual covers the installation programming and commissioning of the Esprit Extinguishing Fire Alarm Control Panels for One and Two Flood Zones www acorn...

Страница 2: ...d EN12094 1 2003 Requirements and test methods for electrical automatic control and delay devices Haes Technologies Ltd declare that the products identified below conform to the essential requirements...

Страница 3: ...4 26 Triggering Signals to Equipment outside the System 4 27 Emergency Abort Device 4 30 Activation of Alarm Devices with Different Signals EN54 2 1997 A1 Control and indicating equipment for fire de...

Страница 4: ...e Standby Current Alarm Current ESG 1002 Esprit Ext Control Panel Single Flood Zone 3 4A PSU 205mA 300mA ESG 1003 Esprit Ext Control Panel Dual Flood Zone 3 4A PSU Large Cabinet 207mA 365mA ESG 1004 E...

Страница 5: ...nnections 19 Connecting the Batteries 19 Battery Charging Voltage Checks 20 Detection Zone Inputs 20 Sounders Monitored Output Circuits 22 Relay Outputs 23 Inputs Class Change and Pulse 24 Monitored I...

Страница 6: ...GAS CARD 57 CONFIG Menu DEVICES 58 CONFIG Menu P BUS 61 CONFIG Menu PSU 61 CONFIG Menu sub menu Breakdown 62 CONTROL Menu 68 Control Menu EXTRACT 68 Control Menu FLOODING 69 Control Menu DELAYS 69 CON...

Страница 7: ...e client s employees and assets are protected to the highest degree with the minimum risk The panels are available in One Flood Zone three Conventional Detection Circuits and Two Flood Zones six conve...

Страница 8: ...IT Gas Extinguishing User Manual PRODUCT OVERVIEW 8 Approved Document Ref UI ESG 01 Issue 2 0 Cabinet for Single Flood Zone Cabinet for Two Flood Zones www acornfiresecurity com www acornfiresecurity...

Страница 9: ...nguishing User Manual PRODUCT OVERVIEW 9 Approved Document Ref UI ESG 01 Issue 2 0 Circuit Boards 2827 206 DISPLAY CARD 2972 206 EXTENSION LEDs CARD 2nd Flood Zone www acornfiresecurity com www acornf...

Страница 10: ...ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW 10 Approved Document Ref UI ESG 01 Issue 2 0 2879 206 PSU CARD 2883 206 GAS CARD www acornfiresecurity com www acornfiresecurity com...

Страница 11: ...sounders outputs to pulse PBUS Note Stage sounders will not be affected unless programmed to do so see program details PBUS Input for RS 485 Peripheral BUS PBUS circuit for remote control call points...

Страница 12: ...W SW Flow switch monitored input Current limit Max 50mA 6K8 EOL PRESS SW Pressure switch monitored input Current limit Max 50mA 6K8 EOL MAN REL Manual release monitored input Current limit Max 50mA 6K...

Страница 13: ...s supply 230VAC 10 15 50Hz max current 0 74Amp 35W for Single flood zone 230VAC 10 15 50Hz max current 2 1 Amp 100W for Dual flood zone Mains supply fuse 2 Amp T2A 250V 35W unit 4 Amp T4A 250V 100W un...

Страница 14: ...oltage 27 3VDC nominal at 20 C for single and dual flood zones Temperature compensated Battery charging output current 700mA Both sizes Current limited Charging supressed During Alarm Condition Batter...

Страница 15: ...e 3v6 Zener diode SOUNDERS 1 2 28VDC polarity reversal monitored sounder outputs to fire alarm devices 6K8 Ohm 5 0 25W EOL resistor Monitoring current limit 28mA fused at 500mA Typical max load 22 dev...

Страница 16: ...ning 21 30VDC 2A continuous rated for solenoids 3A at 450mS available for Metron actuators Monitored inputs 6 FLOW SW PRESS SW MAN REL HOLD ABORT AUTO MAN End of line resistor 6K8 Thresholds 8K to 1K2...

Страница 17: ...e protective earth will render the equipment unsafe Warnings Warning Sign Before installation refer to the ratings shown on the label inside the product and to the Specifications Chart in this documen...

Страница 18: ...ubject to shock or vibration Environments where there is damp salt air water ingress or extremes of temperature must be avoided The temperature should be in the range of 5 C to 40 C and the relative h...

Страница 19: ...ains supply is restored the batteries will be automatically reconnected Note If the mains are connected before the batteries the panel will show a Power Supply fault for up to 1 minute until the monit...

Страница 20: ...tch should be set to ON which will override the temperature compensation controls Carefully adjust the voltage to 29 0VDC 0 2V When completed switch off Access Level 3 DIL switch and re connect the ba...

Страница 21: ...the return key or Enter key as the calibration changes made will be lost and the calibration procedure will need to be repeated Detection Zone Inputs A maximum of 32 detectors per zone only can be fit...

Страница 22: ...e output circuits are provided for single flood zone and six conventional 24VDC programmable and monitored sounder style output circuits are provided for dual flood zone 6K8 End of Line Resistor The s...

Страница 23: ...fter the flooding time has elapsed without a reset This allows a flooded area to be vented of extinguishing medium Local Fire Relay operates on activation of a fire condition in a Flood Zone Stage 1 R...

Страница 24: ...do so see program details Pulse Switch ve inputs which cause the common sounder and detection zone stage sounder s outputs to pulse Note Stage sounders will not be affected unless programmed to do so...

Страница 25: ...ust have a 6k8 resistor fitted at the panel terminals Extinguishing Actuator Output Wiring The circuit is monitored for both open and circuit conditions No EOL resistor needed The output can supply a...

Страница 26: ...on the actuator circuit should be calculated to ensure that the voltage at the end of the circuit exceeds the minimum required by the solenoid typically 18V when the actuator circuit has minimum outpu...

Страница 27: ...d mini RSU require a 4 wire connection 2 wires for 28Vpower 2 wires for RS485 data from the control panel Each RSU has a PCB mounted DIL switch and must be allocated a unique address between 1 and 16...

Страница 28: ...PERATING INSTRUCTIONS Panel Control and Indicators Control Panel The Control Panel contains LCD Display Screen Control Keypads Manual Extinguisher Release Status LED Indicators Activate Controls Key O...

Страница 29: ...uring a fi re or fault condition This function is operational without the need to activate controls Also has the numeric value 3 for code entry Return Press to exit current menu or command as indicate...

Страница 30: ...sounder circuits have been disabled or are in test mode Indicates a fault on one or more sounder circuits Power Supply Fault N A Indicates a power supply fault on mains power input or battery Delay S...

Страница 31: ...in test mode A Fault exists which may prevent the release of extinguishant Manual Only Indicates that extinguishant can only be released by means of a manual release button Briefly indicates during a...

Страница 32: ...de has not been entered Available Functions The functions that can be performed in Access Level 1 are Manually activate the extinguisher release Mute the internal sounder View active faults Change fro...

Страница 33: ...Menu will become available for operation Once the four digit code is entered or the Activate Controls key is turned to On the LCD unit will display the Main Menu Use the Scroll Control keypad up down...

Страница 34: ...3333 is the factory default The access code may be changed from the CONFIG menu PANEL sub menu Available Functions The functions that can be performed at Access level 3 are Set the panel to automatica...

Страница 35: ...ss key o Use the Up Down arrow keys to increase decrease the number value of the first digit in the 4 digit sequence o Use the Left Right arrow keys to move to the next digit in the 4 digit sequence o...

Страница 36: ...isplay shows UNAFFECTED Activated Released Condition The extinguishant Activated Released condition is established for a Flood Zone when Two or more detectors in a single Detection Zone or one or more...

Страница 37: ...ue to be activated to warn that extinguishant has been released Flooding Stage 2 During this phase the now released extinguishant spreads out and settles in the flood zone Gas Released LED continues t...

Страница 38: ...e of extinguishant Flow switch would need a trigger 470 After trigger extinguishant release is started and Gas Released LED illuminated steady Gas Released sounder 2nd Stage Sounder is activated The d...

Страница 39: ...minent countdown is reset to the beginning and restarts Abort Condition If an Extinguishant Abort button is activated in a Flood Zone that is in a Fire Alarm condition the Release Imminent countdown f...

Страница 40: ...fline fault o Fault relay is activated Extension LED board Gas Area 2 LEDs o System Fault LED illuminated continuous o General Fault LED illuminated pulsing o The extension LED Board is halted o Fault...

Страница 41: ...utput options etc Extinguishant release CONTROL Menu Set configurable options for extinguishant release including for FLOOD and EXTRACT Accessing the Menu Structure Power on the panel and wait for it...

Страница 42: ...use Left Right arrow keys to move cursor to CONFIG menu icon Press key to select CONFIG menu The digital display will show the following message Enter Level 3 Access Code Use the keypad to enter code...

Страница 43: ...list containing all 16 RSUs and show if they are connected or not using the P BUS indicated by PRESENT or NOT PRESENT P BUS 1 1st RSU PRESENT NOT PRESENT 2 2nd RSU PRESENT NOT PRESENT 3 3rd RSU PRESE...

Страница 44: ...nter Level 3 Access Code Use the keypad to enter code 3333 o Press key o Use the Up Down arrow keys to increase decrease the number value o Use the Left Right arrow keys to move to the next digit in t...

Страница 45: ...n the required changes are completed press return button to return to DEVICES Menu A short sequence of buzzer beeps will indicate that changes have been stored in memory To go back to the main logo sc...

Страница 46: ...ts are set to the code 1111 press button o The Main Menu will become available for operation Note Access level 2 Menu will deactivate after 30 sec if not used User Menu AUTO MANUAL MODE Menu Used to s...

Страница 47: ...1 SOUNDERS ENABLED DISABLED 2 FIRE Relay ENABLED DISABLED 3 FARE OUTPUT ENABLED DISABLED 4 FAULT Relay ENABLED DISABLED 5 FFRE OUTPUT ENABLED DISABLED GAS AREA ONE 6 Zone ONE ENABLED DISABLED 7 Zone T...

Страница 48: ...turn key to return to User menu User Menu Time Date The Time Date and Set DST sub menus are used to set the system clock and the local Daylight Savings Time Time Date Menu Time Date To set the system...

Страница 49: ...u User Menu LAMP TEST To test the panel LCD display and warning LEDs On the Main Menu use Left Right arrow keys to move cursor box to User menu Press key to select the User menu Under User menu highli...

Страница 50: ...t Right arrow keys to move cursor box to User menu Press key to select the User menu Under User Menu highlight the BUZZER option and then press key to select it Under BUZZER Menu the following option...

Страница 51: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 51 Approved Document Ref UI ESG 01 Issue 2 0 User Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Страница 52: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 52 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 53: ...Left Right arrow keys to move to the next digit in the 4 digit sequence o When all 4 digits have been set to the code 1111 press the key again o The Main Menu will become available for operation Note...

Страница 54: ...following information will be displayed in turn each accompanied by a progress bar o LEARNING INTERNAL CARDS o LEARNING EXTINGUISHANT o LEARNING P BUS On completion of the learning routine the LEARN P...

Страница 55: ...tem Fault status LEDs will be illuminated pulsing with an accompanying fault tone from the internal buzzer Additionally on return to the Title screen a FAULT display will list the applicable faults Th...

Страница 56: ...lue has been selected then the system will return to CONFIG PANEL Menu and all the current settings will be maintained If YES is selected then all current settings will be overwritten and the system w...

Страница 57: ...2 Zone FOUR YES NO 13 Zone FIVE YES NO 14 Zone SIX YES NO 15 CONTRIBUTORY COUNT ONE TWO THREE FOUR Configure the various options for the Gas Card s as follows o Use Left Right arrow keys to toggle bet...

Страница 58: ...LARM YES NO 3 INTRINS SAFE YES NO 4 PRIORITY ALARM ENABLED DISABLED 5 HEAD REMOVAL ENABLED DISABLED 6 Sounder DELAY OFF 10 SEC 20 SEC 30 SEC 1 MIN 90 SEC 2 10 MIN Use Up Down arrow keys to select betw...

Страница 59: ...er HOLD OUTPUT YES NO Note Single Flood Zone Panels will have 4 Sounders 2 Common PSU Card Sounders and 2 Sounders for the Gas Card Dual Flood Zone Panels will have 6 Sounders 2 Common PSU Card Sounde...

Страница 60: ...10 EVAC CONTINUOUS PULSING OFF 11 FAULT CONTINUOUS PULSING OFF 12 FAIL YES NO 13 EXTRACT AREA 1 YES NO 14 EXTRACT AREA 2 YES NO Note Single Flood Zone Panels will have 6 Relays 2 common Relays on the...

Страница 61: ...return to CONFIG Devices menu A short acknowledgement sound will be present Note Any differences between detected devices and changes made by user will result in a General Fault condition The General...

Страница 62: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 62 Approved Document Ref UI ESG 01 Issue 2 0 CONFIG Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Страница 63: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 63 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 64: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 64 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 65: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 65 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 66: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 66 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 67: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 67 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 68: ...display will show the following message Enter Level 3 Access Code Use the keypad to enter code 3333 o Press key o Use the Up Down arrow keys to increase decrease the number value o Use the Left Right...

Страница 69: ...ll be presented as follows FLOODING AREA ONE AREA TWO STOP STOP STATE STATE FLOODING OFF FLOODING OFF Use Left Right arrow keys to move between Flood Zone Areas dual flood zone panels only Press the k...

Страница 70: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 70 Approved Document Ref UI ESG 01 Issue 2 0 CONTROL Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Страница 71: ...to increase decrease the number value o Use Left Right arrow keys to move to the next digit in the 4 digit sequence o When all 4 digits have been set to the code 1111 press the key again The Main Menu...

Страница 72: ...he return key or key to return to the Main Menu display Report Menu FAULT From the FAULT sub menu the number of FAULT events is displayed To get FAULT events information On the Main Menu use Left Righ...

Страница 73: ...nu will become available for operation On the Main Menu use Left Right arrow keys to move cursor to Report menu icon and press key to select From the Report Menu use Left Right arrow keys to move curs...

Страница 74: ...Left Right arrow keys to move curser to select OTHER sub menu Press key to select The number n of OTHER events will be displayed in the following manner OTHER A 00 F 00 D 00 O nn List of detected oth...

Страница 75: ...ENT HISTORY will open e g nnnn PANEL RESET nnnn BATTERY MISSING nnnn MAINS FAIL Note Where nnnn represents an automatically assigned four digit sequential number allocated to each event Use the Up Dow...

Страница 76: ...ress key to select the Report menu Under Report Menu select the COUNTER option and then press key to access it The ALARM COUNT sub menu will open and the following information will be available ALARM...

Страница 77: ...SU Card To get status information for the panel s PSU card On the Main Menu use Left Right arrow keys to move cursor box to Report menu Press key to select the Report menu Under Report Menu select the...

Страница 78: ...Manual CONFIGURING THE PANEL 78 Approved Document Ref UI ESG 01 Issue 2 0 Next press return key or key to return to the Report Menu A short acknowledgement sound will be present www acornfiresecurity...

Страница 79: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 79 Approved Document Ref UI ESG 01 Issue 2 0 Report Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Страница 80: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 80 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 81: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 81 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 82: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 82 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Страница 83: ...in the zone s in test detectors call points etc can be activated and the panel will automatically reset enabling the system to be tested by one person Under the Test MODE sub menu the following sub m...

Страница 84: ...NERAL 1 SOUNDERS EXCLUDED TESTING GAS AREA ONE 2 Zone ONE EXCLUDED TESTING 3 Zone TWO EXCLUDED TESTING 4 Zone THREE EXCLUDED TESTING GAS AREA TWO for twin Flood Zone panels 5 Zone FOUR EXCLUDED TESTIN...

Страница 85: ...to move curser to select MISC sub menu Press key to select The MISC OPTIONS menu will now be displayed as follows 1 REMOVE ALL Disablement Highlight the REMOVE ALL Disablement option and press key to...

Страница 86: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 86 Approved Document Ref UI ESG 01 Issue 2 0 ENG Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Страница 87: ...indicating venting aperiodic load test with the Mains supply disabled to ensure adequate battery capacity Both batteries should be renewed if there is any doubt about their integrity The memory log sh...

Страница 88: ...www haes Tech com www acornfiresecurity com www acornfiresecurity com...

Отзывы: