ESPRIT Gas Extinguishing User Manual
OPERATING INSTRUCTIONS
35
Approved Document Ref: UI-ESG-01 Issue 2.0
•
The
ALARM COUNT
sub-menu will open, and the following information will be available:
ALARM COUNT: nnnn
(number (
n
) of alarm events that have occurred)
LAST ALARM AT: dd-MMM-yy hh:mm:ss
(date and time when the last event
happened)
HOLD DOWN SELECT TO RESET:
•
To reset the alarm count, press and hold down
✓
key and the following will be displayed:
Enter Level 4 Access Code
0 _ _ _
•
Use the keypad to enter code 4444:
o
Press
✓
key
o
Use the Up/Down arrow keys to increase/decrease the number value of the first digit
in the 4-digit sequence.
o
Use the Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code 4444 press
✓
key once again.
•
This action will clear to zero the value of any Alarm Count (if more than zero). A short
acknowledgement sound will be present.
•
Press return
key to return to
Report Menu
.
Available Functions
The functions that can be performed at Access level 4 are:
•
Reset the ALARM COUNT
Engineer (Access Level 4) Options
The Engineer (Access level 4) option prevents accidental resetting of the Alarm count data.