ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
61
Approved Document Ref: UI-ESG-01 Issue 2.0
CONFIG Menu: P-BUS
To configure the P-BUS, access the
P-BUS
menu.
•
From the
CONFIG
sub-menu, highlight
P-BUS
option and then press the
✓
key in order to gain
access to it.
•
The information available under
CONFIG P-BUS
will be presented as follows:
-P-BUS-
1: FIRST RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
2: SECOND RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
3: THIRD RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
to
14: FOURTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
15: FIFTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
16: SIXTEENTH: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
•
If, since the last panel LEARN routine, RSU(s) have been added to, or removed from, the
P-BUS, their status can be changed manually:
o
Use the Up/Down arrow keys to select which RSUs are to be configured.
o
Press
✓
key to change between
GAS AREA ONE/GAS AREA TWO/NOT
PRESENT
o
Press the return
key once to return to
CONFIG Devices
menu. A short
acknowledgement sound will be present.
Note:
Any differences, between detected devices and changes made by user, will result in a
General Fault condition. The
General Fault
status LED will be illuminated pulsing, with an
accompanying fault tone from the internal buzzer. Additionally, on return to the Title screen, a
FAULT
display will list the applicable faults (i.e. ‘1: RSU RSU 01 OFFLINE’). This condition
will require the panel to be re-configured to clear.
CONFIG Menu: PSU
To configure Power Supply Unit settings, access the
CONFIG PSU
menu:
•
From the
CONFIG
sub-menu, highlight
PSU
option and then press the
✓
key in order to gain
access to it.
•
The information available under
CONFIG PSU
menu will be presented as:
1: BATTERY MONITORING: YES/NO
2: BATTERY HIGH-Z MONITORING: YES/NO
3: CHARGE DURING ALARM: YES/NO
4: EARTH FAULT MONITORING: YES/NO
5: UPS MODE: YES/NO
•
Use the Up/D\own arrow keys to navigate between options 1
–
5.
•
Press
✓
key to change between
YES
or
NO
values, as required, for each option.
Next press the return
key to return to
CONFIG MENU
. A short acknowledgement sound will be
present.