ESPRIT Gas Extinguishing User Manual
CONFIGURING THE PANEL
84
Approved Document Ref: UI-ESG-01 Issue 2.0
Note:
OFF
will de-activate Test Mode function, so that any zones set for this mode will still activate
Fire Alarms in the standard way
•
When selection is made, press return
key to return to
Test MODE
sub-menu screen.
Test MODE Menu: SETTINGS
This menu is used to set which zone(s) are to be tested, along with Sounder option:
•
On the
Main Menu
, use Left/Right arrow keys to move cursor to
ENG
menu icon and press
✓
key to select.
•
From the
ENG Menu
, use Left/Right arrow keys to move curser to select
Test
sub-menu.
Press
✓
key to select.
•
On the
Test MODE
menu, use Left/Right arrow keys to select
SETTINGS
sub-menu. Press
✓
key to select.
•
The
Test SETTINGS
menu will display the following options:
-GENERAL-
1: SOUNDERS: EXCLUDED / TESTING
-GAS AREA ONE-
2: Zone ONE: EXCLUDED/TESTING
3: Zone TWO: EXCLUDED/TESTING
4: Zone THREE: EXCLUDED/TESTING
-GAS AREA TWO-
(for twin Flood Zone panels)
5: Zone FOUR: EXCLUDED/TESTING
6: Zone FIVE: EXCLUDED/TESTING
7: Zone SIX: EXCLUDED/TESTING
•
Use the Up/Down arrow keys to select the required option.
•
Press
✓
key to toggle between
Excluded
and
Testing
.
Press return
key to accept and return to
Test MODE
sub-menu.
Press return
key to accept and return to
ENG
menu.
Note:
The indicated states are either
EXCLUDED
(i.e. excluded from Test) or
TESTING
(i.e. included
in the Test). Any zones set to
TESTING
will create a non-latching fire alarm with unaffected Release
status when activated, without any sounder activation, unless sounders have been included in the test
in which case, they will all pulse twice then go silent. Sounders if set for testing will still operate normally
to fires detected on zones excluded from testing.