ESPRIT Gas Extinguishing User Manual
OPERATING INSTRUCTIONS
33
Approved Document Ref: UI-ESG-01 Issue 2.0
OTHER
A00 F00 D00 O01
1: MANUAL MODE AREA 1 ON RSU nn
Note:
The system may have many inputs for selecting Manual Only Mode, from RSUs or mini RSUs
connected to the system. Any one of these set in the manual condition will override the main panel
setting. All must be set to automatic to return the status to Automatic/manual mode.
Authorized User Controls
The Authorised User (Access level 2) controls can be accessed by:
•
Turning the
Activate Controls
key clockwise to the
On
position. The padlock symbol will show
unlocked and all the buttons on the keypad will be operational. To deactivate the controls, turn
the key back to the
Off
position. The padlock symbol will show locked.
or
•
Entering four-digit access code 1111
o
Press the
✓
key
o
Use the Up/Down arrow keys to increase/decrease the number value
o
Use the Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code
1111,
press enter
✓
key once again
o
The
Main Menu
will become available for operation.
Once the four-digit code is entered, or the
Activate Controls
key is turned to
On
, the LCD unit will
display the
Main Menu
. Use the Scroll Control keypad up/down and left/right arrows, and the enter
✓
key to navigate the Access level 2 menu.
Note:
If the Activate Controls key is in the
On
position, the keypad will remain active.
Note:
It is not possible to remove the key, whilst it is in the
On
position.
Note:
The padlock symbol is shown on the LCD screen, to the right of the Time and Date indication.
Note:
The Access level 2 code 1111 is the factory default. The access code may be changed from the
CONFIG
menu
PANEL
sub-menu.
Available Functions
The functions that can be performed at Access level 2 are:
•
Resound the alarms
•
Silence the alarms
•
Reset the system
•
Mute the internal sounder
•
Access the Authorised User (Access level 2) menu structure, from the icons on the
Main Menu
•
Access the
CONFIG
menu or
CONTROL
menu (Access level 3) Engineer controls, for
configuration and commissioning of the system, by entering the Engineer Access level 3 four-
digit access code.
Authorised User Menu Options
The Authorised user (Access level 2) menu options are available from the
Main Menu
:
•
User
•
Report
•
ENG
www.acornfiresecurity.com
www.acornfiresecurity.com