Testing PLC Systems
LT51 User Manual
21
Adjust the span to 4.5 kHz by pressing the [f1] soft key, then turning the
knob to increase or decrease the span.
4. In spectral mode, move the marker using the knob to read the level at each
frequency peak.
5. Add 40 dB to each reading because of the 40dB attenuator.
Example Measurement results for 3 frequencies:
Frequency
(Hz)
Theoretical
level
Measured levels
(with 40 dB attenuator)
Tx pilot
499820
+26 dBm
-14.00 + 40 = +26 dBm
Rx pilot
500180
0 ± 2 dBm*
-40.00 + 40 = 0 dBm*
External tone
(3800 Hz)
496200
+32 dBm
-7.98 + 40 = +32 dBm
* reception level is attenuated by 28dB ± 2 dB
Press to display the frequency spectrum:
Press to display the level at different centre frequencies:
499.820 kHz for the TX pilot
500.180 kHz for the RX pilot
496.200 kHz for the external 3800 Hz tone