Testing PLC Systems
LT51 User Manual
24
Measuring the Blocking Impedance of Line Traps
Figure 4.3: Test Setup
– Measuring PLC Trap Impedance with LT51
1. Connect the RTX a-b terminals to the PLC Line Trap as shown.
2. Press the key, followed by the [f4] soft-key to set the
“Mag Z”
measurement mode.
3. Set the desired TX frequency, by pressing the key, followed by the
[f4] “TX Freq” soft-key. Use the Knob or Keypad, and then press the
button to clear the Dialog box, or appropriate [fx] soft-key if using keypad.
OR
Press the key to show a graph of the Impedance Magnitude vs.
Frequency over the selected frequency span.
Press the key, followed by the [f1] “Span” soft-key to set the desired
frequency span.
This is the only
earth point of
measuring circuit
To Disconnector
in OPEN position
PLC
Line
Trap
Line dropper to
overhead line
Overhead
line must be
switched off
and earthed
by auxiliary
earth
connection