K-BUS
®
KNX/EIB
Universal Interfaces
33
Parameter “Connect contact type”
This parameter defines whether the contact at the input is a normally open contact or a normally
closed contact.Options:
Normally closed
Normally open
The parameter introduced in this chapter is use “Normally open” as the example, the normally close
is just opposite.
Parameter “Operation functionality type”
This parameter defines the types of the shutters operation, detailed description of the type and
function as the following table:
1-push-button,short=stepping, long=moving
Short operation
Alternate implement “Stop/Adjust upward” or “Stop/Adjust downward”
operation
(
alternate send the value of the object “0”and“1”
)
Long operation
Alternate implement “Move up” or “Move down” operation
(
alternate send the value of the object “0”and“1”
)
1-push-button, short=moving, long=stepping
Short operation
Alternate implement “Move up” or “Move down” operation
(
alternate send the value of the object “0”and“1”
)
Long operation
Alternate implement “Stop/Adjust upward” or “Stop/Adjust downward”
operation
(
alternate send the value of the object “0”and“1”
)
1-push-button-operation, moving
Operation
When operation
,
send the command in sequence
:
……
-
>Move up
-
>Stop/Adjust upward
-
>Move down
-
>Stop/Adjust
downward
-
>……
1-switch-operation, moving
Operation start
(
press the button
)
Alternate implement “Move up” or “Move down” operation
(
alternate send the value of the object “0”and“1”
)
Operation end
(
Release the button
)
Stop/Adjust
2-push-button, standard
Short operation
“Stop/Adjust upward” or “Stop/Adjust downward”
(
set by parameter
)
Long operation
“Move up” or “Move down”
(
set by parameter
)