Parameter “Reaction on closing the contact (rising edge)”
Parameter “Reaction on opening the contact (fall edge)”
This parameter is visible if there is no distinction between a short and long operation. It can be set
the operation to open and close the contact.Options:
No action
Off
On
Toggle
Stop cyclic transmission
If the parameter “Toggle” is selected, negate the operation, that means negate the current value. For
example, if “On” is selected, when negate it will carry out “Off” operation. If the parameter “Stop cyclic
transmission” is selected, it will stop the cyclical sending telegram till there is a new object value to be
sent. If the parameter “No action” is selected, it will not implement any operation.
Parameter “Interval of Tele. Cyclic send: Base× Factor”
This parameter is used to set the interval time between two telegrams that are sent cyclically, it is
visible if cyclical sending has been set. Transmission cycle time =Base× Factor.
Base options:
1s
10s
…
1h
Factor options:
1…255
Parameter “Send object value after voltage recovery (if yes not equal toggle)”
It can be set whether to send the value of the object “Tele. Switch, X” on the bus after voltage
recovery, this parameter is visible if there is no distinction between a short and long operation.Options:
No
Yes
If the parameter “Yes” is selected, it will send the current value of the object “Tele. Switch, X” on the
bus. Only when the value “Toggle” has not been set in either of the two parameters “Reaction on
opening/closing the contact”, the value of the object “Tele. Switch, X” can be send on the bus. If one of
the two parameters has the value “TOGGLE”, no values are sent in general on the bus after bus voltage
recovery. If “No reaction” or “Stop cyclic transmission” is selected, there is no values are sent on the bus
either.