K-BUS
®
KNX/EIB
Universal Interfaces
13
is selected, the push button action need to delay to determine whether the operation is long or short. In
this case, the lighting is dimmed via a long operation and switched via a short operation.
Parameter “Reaction on short operation”
This parameter is visible if the value “Dimming and switching” has been set in the parameter
“Dimming functionality”. It is able to set the operation after triggered the object “Switch, X”, that’s a short
operation.Options:
No action
Off
On
Toggle
Parameter “Reaction on long operation”
This parameter is visible if the value “Dimming and switching” has been set in the parameter
“Dimming functionality”. It is able to set a dim brighter or a dim darker after a long operation.Options:
Dimming brighter
Dimming darker
Dim brighter/darker with start brighter
Dim brighter/darker with start darker
The parameter “Dim brighter/darker with start darker” is selected, it can be dim brighter or dim
darker after a long operation, it is just dim darker first and the latter operation negate.
Note: The long and short operation is individual; they are not operation on one object.
Parameter “Long operation after”
This parameter is visible if the value “Dimming and switching” has been set in the parameter
“Dimming functionality”. The period TL is defined here, after which an operation is interpreted as
“long”.Options:
0.3s
0.5s
……
10s
Parameter “Reaction on operation”
This parameter is visible if the value “Only dimming” has been set in the parameter “Dimming