K-BUS
®
KNX/EIB
Universal Interfaces
20
Control the scene via “5 separate objects”:
Parameter value
Behaviour
On long operation
As soon as a long operation is detected, the object
“Store scene, X” sends the value “1” on the bus and
the object “Output 1bit/8bit, group A…E” send read out
telegram. The objects “Output 1bit/8bit, group A…E”
can be modified via the bus for the duration of the long
operation.
Once the long operation has finished, the
object“Store scene, X” sends the value “0” on the bus
and the current object values can’t be modified
On the long operation, If the object “Store scene, X”
receives the value “0” on the bus, even the long
operation has not finished ,the current object value
also can’t be modified
If object value= ‘1’
If the object “Store scene, X” receives the value “1”,
the object values “Output 1bit/8bit, group A…E” are
read out via the bus. While the object value is “1”, the
objects “Output 1bit/8bit, group A…E” can be modified
via the bus.
On receipt of the object value “0”, the current object
values can’t be modified
On long operation and object value= ‘1’
If the object “Store scene, X” receives the value “1”
on the bus, on the next long operation, the object
“Output 1bit/8bit, group A…E” read out the telegram.
The objects “Output 1bit/8bit, group A…E” can be
modified via the bus for the duration of the long
operation. After the end of the long operation, the
object values can’t be modified
,
the object “store
scene, X” will send value ‘0’
On the long operation, If the object “Store scene, X”
receives the value “0” on the bus, even the long
operation has not finished ,the current object value
also can’t be modified
Provided that a “1” has not been received at the object
“Store scene, X”, a long operation is interpreted in the
same way as a short operation.