K-BUS
®
KNX/EIB
Universal Interfaces
26
Closing contact (rising edge)
Opening contact (falling edge)
The parameter introduced in this chapter is use “Closing contact (rising edge)” as the example, the
operation of opening contact is just opposite.
Parameter “LED status on pulse detection”
This parameter defines the indication of LED, whether to be on, off or no action when detect there is
pulse input.Options:
LED A ON
LED A OFF
……
DED D OFF
No action
Note: If the four channels invocate the same option, the priority of channel A is the highest, it
will carry out the preset operation when detected pulse input. Then the priority of channel B is
higher, then it’s C, the last is D. The priority of LED X in function channel in the device is higher
than the LED X channel, the LED X can not be implement any operation in channel LED X which
is used in the function channel in the device. If the parameter “LED status on pulse detection” is
set “LED A ON” or “LED A OFF” options, the operation had been set in LED A can not be carry
out.
Parameter “Date width of counter”
The data type of the counter (absolute counter and differential counter) is defined in this parameter.
The data type specifies the counting range for the counter.
The type of the objects “Output counter value……” and “Differential counter …” is adapted to the
data type of the parameter setting.Options:
8bit [0…255]
16bit [-32768…32767]
16bit [0…65535]
32bit [-2147483648…2147483647]
Parameter “Counter starts at”
The starting value of the absolute counter is defined in this parameter. When the bus power on, it
will calculate the new counter value from this preset starting value.