K-BUS
®
KNX/EIB
Universal Interfaces
28
Fig.13 Parameter window “Counter-X”
Parameter “Divider: number of input pulse for one counter step[1…32767]”
It can be set via this parameter how many pulses are necessary to generate a counting pulse. The
range of pulse import-ability:
1…32767
.
Parameter “Factor: one counter step changes counter value by [-32768…32767]”
This parameter defines how much the counter and differential counter should be increased by in the
event of a counting pulse. Range:
-32768…32767
Parameter “Send counter value cyclically”
This parameter defines whether to send the current value cyclically. If this parameter has the value
“Yes”, the values of the counter and the differential counter are sent cyclically on the bus.Options:
No
Yes
Parameter “Base”/ “Factor [1…255]”
It is visible if the parameter “Send counter value cyclically” is “Yes”. This parameter is used to set the
interval time between two telegrams that are sent cyclically, Transmission cycle time =Base× Factor.
Base options:
1s
10s
…
1h
Factor options:
1…255