K-BUS
®
KNX/EIB
Universal Interfaces
17
Parameter “Reaction on short operation”/ “Reaction on long operation”
This parameter is visible if there is no distinction between a short and long operation. It defines the
data type that is sent after a short or long operation.Options:
1 bit value [0, 1]
……
4 byte value [0…4294967295]
Parameter “Output value […]”
This parameter defines the value which is sent on operation. The value range is dependent on the
selected data type. Two values can be set here when there is a distinction between a short and long
operation.
Parameter “Long operation after: Base× Factor [0…255]
This parameter is visible if there is a distinction between a short and long operation. The period TL is
defined here, after which an operation is interpreted as “long”. TL = Base x Factor.
Base options:
100s
1s
…..
1h
Factor options:
2~255
Parameter “Send object value after voltage recovery”
This parameter defines whether to send object value of “Tele. Value, X” on the bus after the voltage
recovery. This parameter is visible if there is no distinction between a short and long operation. If “yes” is
selected, the device sends the object “Tele. Value, X” on the bus after bus voltage recovery.Options:
No
Yes
Parameter “Debounce time”
It can set the vibration time to prevent unwanted multiple operation by bouncing of contacts in
vibration time, which means the effective time of the contact operation.Options:
10ms
20ms
……
150ms
Min. operation
A minimum operation time can only be set if there is no distinction between a short and long
operation. The parameter window will be shown in Fig. 3.