60
Expert Power Control 8021/8025
© 2021 GUDE Systems GmbH
Specifications
Reverse Reactive Energy counter.
epc8025RevEnergyActiveReset-
table
.79.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc8025RevEnergyReactiveReset-
table
.79.1.5.1.2.1.23.x
Gauge32
RO
Resettable Reverse Reactive Energy counter.
epc8025ResidualCurrent
.79.1.5.1.2.1.24.x
Unsigned32
RO
Actual Residual Current on Power Channel. According Type A IEC
60755. Only visible on models that support this feature.
epc8025ResidualCurrentRMS
.79.1.5.1.2.1.25.x
Unsigned32
RO
Actual Residual Current RMS on Power Channel. According Type B IEC
60755. Only visible on models that support this feature.
epc8025ResidualCurrentDC
.79.1.5.1.2.1.26.x
Unsigned32
RO
Actual Residual Current DC on Power Channel. According Type B IEC
60755. Only visible on models that support this feature.
epc8025LineSensorName
.79.1.5.1.2.1.100.x
OCTETS
RW
A textual string containing name of a Line Sensor
epc8025OVPIndex
.79.1.5.2.1.1.x
Integer32
RO
None
epc8025OVPStatus
.79.1.5.2.1.2.x
INTEGER
RO
shows the status of the built-in Overvoltage Protection
epc8025spActivePowerChan
.79.1.5.5.1.0
Unsigned32
RO
Number of Single Port Power Channels. Value is zero on EPC 8220
series.
epc8025spPowerIndex
.79.1.5.5.2.1.1.x
Integer32
RO
Index of Single Port Power Channel entries. Indices 0-5 mean Ports A1
to A6, 6-11 are Ports B1 to B6.
epc8025spChanStatus
.79.1.5.5.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8025spAbsEnergyActive
.79.1.5.5.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc8025spPowerActive
.79.1.5.5.2.1.4.x
Integer32
RO
Active Power
epc8025spCurrent
.79.1.5.5.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
epc8025spVoltage
.79.1.5.5.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc8025spFrequency
.79.1.5.5.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc8025spPowerFactor
.79.1.5.5.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc8025spPangle
.79.1.5.5.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc8025spPowerApparent
.79.1.5.5.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc8025spPowerReactive
.79.1.5.5.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc8025spAbsEnergyReactive
.79.1.5.5.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc8025spAbsEnergyActiveReset-
table
.79.1.5.5.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset-
table counter.
epc8025spAbsEnergyReactiveRe-
settable
.79.1.5.5.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc8025spResetTime
.79.1.5.5.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc8025spForwEnergyActive
.79.1.5.5.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc8025spForwEnergyReactive
.79.1.5.5.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc8025spForwEnergyActiveRe-
settable
.79.1.5.5.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc8025spForwEnergyReact-
iveResettable
.79.1.5.5.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc8025spRevEnergyActive
.79.1.5.5.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc8025spRevEnergyReactive
.79.1.5.5.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc8025spRevEnergyActiveReset-
table
.79.1.5.5.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
Содержание Expert Power Control 8021 Series
Страница 2: ...2 Expert Power Control 8021 8025 2021 GUDE Systems GmbH...
Страница 5: ...Device Description...
Страница 14: ...Operating...
Страница 24: ...Configuration...
Страница 51: ...Specifications...
Страница 92: ...Support...