![Gude Expert Power Control 8021 Series Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/gude/expert-power-control-8021-series/expert-power-control-8021-series_manual_2277611067.webp)
67
Expert Power Control 8021/8025
© 2021 GUDE Systems GmbH
Specifications
Public Keys
RSA and ECDSA public keys are accepted.
Generated keys can be copied directly from e.g. putty gen,
and inserted into the Configuation - Console input field. Public keys are accepted in
SSH2 or OpenSSH format.
4.7.2
Push Messages
On the console channels (Telnet, SSH or serial console) push messages can be activ-
ated, which output sensor values in time intervals (every n seconds) or from an ad-
justable change of the sensor value threshold on this channel. The generated mes-
sage always starts with a "#" and ends with a CR/LF. This also applies to sensor limit
value messages if "Console" is selected as message channel in Sensors - Configura-
tion.
If you open a Telnet or SSH connection, you can use "console telnet pushmsgs set 1"
or "console ssh pushmsgs set 1" to temporarily activate the push messages. From now
on push messages will be sent asynchronously on this channel. The asynchronicity of
the messages can cause problems on a connection if you send commands yourself.
Then there are the possibilities:
·
Filter all incoming characters between "#" and CR/LF
·
or open a second channel (Telnet, SSH, serial) and activate Push Messages
Содержание Expert Power Control 8021 Series