Device Description
Recovering of the overvoltage protection function can only be performed by the
manufacturer of the device. In the normal case, the device will continue to work even
after the failure of the protective function.
A signaling via E-Mail, Syslog or SNMP trap occurs only once during operation, ex-
actly at the moment in which the protection fails. In addition, at the start up of the
device a message is generated, when the overvoltage protection is not active.
1.6
Technical Specifications
Interfaces
1 x Mains supply (IEC C20, max.16 A)
1 x Ethernet port (RJ45)
1 x Serial connector (D-SUB, RS232)
2 x RJ45 for external sensor
Load Outputs
8021-1 / 8025-1
4 x Load Outputs (IEC C13, max. 10 A)
Load Outputs
8021-2 / 8025-2
4 x Load Outputs (IEC C13 Lock, max. 10 A)
Network connectivity
10/100 MBit/s 10baseT Ethernet
Protocols
TCP/IP, HTTP/HTTPS, SNMP v1/v2c/v3,
SNMP traps, Syslog, E-Mail (SMTP)
Power Supply
internal power supply (100-240 V AC / -15% /
+10%, 50-60 hz)
Overvoltage Protection: 20mm / 250J varistor disk (300V AC)
·
single peak current for 20/80us pulse: 10000 A
·
max. clamping voltage 20/80us pulse, Ipk = 100 A: 775 V
Environment
·
Operating temperature
·
Storage temperature
·
Humidity
0°C - 50 °C
-20°C - 70 °C
0% - 95% (non-condensing)
Case
powder coated, galvanized steel sheet
Measurements
19" (inches), 1 Rack Unit, (Depth 195 mm)
Weight
approx. 2.9 kg (
8021
)
approx. 3.0 kg (
8025
)
1.6.1
Electrical Measurement
typical fault tolerances for Ta=25°C, I=1Arms...16Arms, Un=90Vrms...265Vrms