background image

Expert Power Control 8021 Series
Expert Power Control 8025 Series

© 2021 GUDE Systems GmbH

Manual Ver. 1.1.0

from Firmware Ver. 1.1

Manual

Содержание Expert Power Control 8021 Series

Страница 1: ...Expert Power Control 8021 Series Expert Power Control 8025 Series 2021 GUDE Systems GmbH Manual Ver 1 1 0 from Firmware Ver 1 1 Manual...

Страница 2: ...2 Expert Power Control 8021 8025 2021 GUDE Systems GmbH...

Страница 3: ...directly 15 2 2 Control Panel 15 2 3 Maintenance 17 2 3 1 Maintenance Page 19 2 3 2 Configuration Management 20 2 3 3 Bootloader Activation 21 3 Configuration 24 3 1 Power Ports 25 3 1 1 Watchdog 26...

Страница 4: ...4 5 SNMP 54 4 5 1 Device MIB 8021 56 4 5 2 Device MIB 8025 58 4 6 SSL 61 4 7 Console 63 4 7 1 SSH 66 4 7 2 Push Messages 67 4 7 3 Console Cmd 8021 68 4 7 4 Console Cmd 8025 76 4 7 5 Serial Console 85...

Страница 5: ...Device Description...

Страница 6: ...t not be used in condensing or excessively hot environments Please also observe the other instructions in the instructions for proper handling of the device Because of safety and approval issues it is...

Страница 7: ...upport with public key and passwords Individually parameterisable switch on delay of all outputs Programmable timetables and turn on turn off sequences Individually adjustable watchdog for each output...

Страница 8: ...wer consumption 7 segment display In the Revision 2 model variant with new display 1 2x 7 segment displays partly with unit LEDs 2 4 plain text indicators on off for the status of the outputs 3 Status...

Страница 9: ...vervoltage Protection The device contains an overvoltage protection The protection is based on input side varistors with thermal fuse between phase L and neutral N to protect the internal electronics...

Страница 10: ...D SUB RS232 2 x RJ45 for external sensor Load Outputs 8021 1 8025 1 4 x Load Outputs IEC C13 max 10 A Load Outputs 8021 2 8025 2 4 x Load Outputs IEC C13 Lock max 10 A Network connectivity 10 100 MBit...

Страница 11: ...Var 1 1 5 Apparent power 0 4000 VA 1 1 5 Power factor 0 1 0 01 3 Energy Counter Active Energy total 9 999 999 999 kWh 0 001 1 5 Active Energy temporary 9 999 999 999 kWh 0 001 1 5 1 7 Sensor Two exter...

Страница 12: ...imum and 1 C typical 20 C to 80 C at 2 C maximum and 1 C typical air humidity range non condensing 0 100 3 maximum and 2 typical 0 100 3 maximum and 2 typical air pressure range full 1 hPa typical at...

Страница 13: ...ated by the green LED on the sensor port that is lit permanently The sensor values are displayed at the Control Panel web page A click on the link in the Name column opens the display of the Min and M...

Страница 14: ...Operating...

Страница 15: ...LED for the first output starts blinking i e the output is selected Press Select again to select the next output If you keep the Ok but ton pressed for one second the state of the selected output wil...

Страница 16: ...8021 8025 a panel with buttons to control a single port appear The Port icon is green when the relay is closed or red in the open state An additional small clock icon indicates that a timer is active...

Страница 17: ...www gude info wiki 2 3 Maintenance The actual device generation with IPv6 and SSL allows all maintenance functions in the web interface to be carried out on the Maintenance Page Maintenance in the web...

Страница 18: ...see chapter Bootloader activation The following functions can be executed using the GBL_Conf exe application Set IPv4 address net mask and gateway Turn HTTP password on and off Turn IP ACL on and off...

Страница 19: ...tloader mode see chapter Bootloader activation All TCP IP settings are reset in this operation If a unit is set to factory defaults an uploaded certificate or updated firmware will be preserved 2 3 1...

Страница 20: ...f the Telnet console If the configuration of a device is to be restored from a text file load the file with Upload and restart the device with Restart Device Saving the configuration should only be ca...

Страница 21: ...principle also be transferred in a Telnet session but then the settings are changed during operation and not completely when restarting as it would have been the case with an upload It can happen that...

Страница 22: ...ge is maintained Abandonment of the Bootloader Mode 1 via push button Hold both buttons for 3 seconds only if the device has 2 buttons 2 or Remove and connect the power supply without operating a butt...

Страница 23: ...23 Expert Power Control 8021 8025 2021 GUDE Systems GmbH Operating The status LED will blink in a fast rhythm please wait until the LED blinks slowly about 5 seconds...

Страница 24: ...Configuration...

Страница 25: ...sed to select the power ports to be con figured Label You can assign a name up to 15 characters for each of the power ports Using the name an identification of the the device connected to the port can...

Страница 26: ...AS systems The mode IP master slave port allows you to switch a port depending on the availability of a remote device When a watchdog is activated it presents various information in the Control Panel...

Страница 27: ...longer a reply after a set time the watchdog performs the specified action usually a reset of the Power Port Now the watchdog waits until the monitored device reports again on the network This may ta...

Страница 28: ...TCP IP settings should be obtained directly from the DHCP server When the function is selected each time the device powers up it is checked if a DHCP server is available on the network If not the las...

Страница 29: ...device leads by no means to a change of the relay states Manual IPv6 Configuration The input fields for the manual setting of IPv6 addresses allow you to configure the prefix of four additional IPv6...

Страница 30: ...on Selects whether access is possible only with HTTP HTTPS or both Server port HTTP Here can be set the port number of the internal HTTP Possible val ues are from 1 to 65534 default 80 If you do not u...

Страница 31: ...stored locally In this case an admin password and a user password must be assigned The password can have a maximum of 31 characters The name admin and user are provided for the user name in the passwo...

Страница 32: ...s port Raw mode The VT100 editing and the IAC protocol are disabled Active negotiation The IAC negotiation is initiated by the server Activate echo The Telnet echo setting if not changed by IAC Push m...

Страница 33: ...y Delete public key Setting this at Apply deletes the public key Enable serial console Enables the serial console Raw mode The VT100 editing is disabled Activate echo The echo setting Enable binary KV...

Страница 34: ...n 3 3 2 Syslog Enable Syslog Enables the usage of Syslog Messages Syslog Server If you have enabled Syslog Messages enter the IP address of the server to which the syslog information should be transmi...

Страница 35: ...aceholder since for security reasons the device never stores the password itself but only the key formed using the Authorization Algorithm If you want to change a pass word the complete password must...

Страница 36: ...compatibility reasons only use ASCII char acters Timeout How long in seconds will be waited for a response from an Authentication Request Retries How often an authentication request is repeated after...

Страница 37: ...Test Password Password input field for Radius test The Test Radius Server function allows you to check whether a combination of User name and Password is accepted by the configured Radius Servers 3 3...

Страница 38: ...the second NTP server Used when the first NTP server does not respond Timezone The set time zone for the local time Daylight Saving Time If enabled the local time is converted to Central European Sum...

Страница 39: ...the dialog for advanced timer settings 3 4 3 Timer Configuration There are three possibilities in the timer configuration Create a simple timer add an advanced timer or change an existing configurati...

Страница 40: ...9 30 a m and switched off after 1 5 hours A click on Save saves this rule For example using only one timer rule to turn on a port at 9 00 and turn it off at 20 00 If at 9 00 the timer is triggered a b...

Страница 41: ...o changes by one This also applies to the index in the console commands A simple timer is directly enabled on a new complex timer the enable trigger option must be switched on manually You can set a p...

Страница 42: ...s only active between October and December also the action does not take place on the first day of a month Since all fields in the mask are always taken into account it is not possible to define the t...

Страница 43: ...a random trigger probability of 90 In addition to port 1 port 5 is activated here and deactivated again after 90 minutes A popup at the mouse pointer shows the port number of the corresponding field...

Страница 44: ...r time you cannot do it directly with a simple timer Therefore it can be useful to first cre ate the timer as a simple timer and then adjust it in the extended dialog Switches port 3 on every day at 9...

Страница 45: ...in order to confuse potential burglars you do not always want to raise and lower the blinds at the same times A jitter of 1800 seconds means that the action is performed randomly between 30 minutes b...

Страница 46: ...Selects a data channel from a sensor Enable Messages Enables the generation of sensor messages Maximum Minimum value Here you can choose whether and at what Maximum Min imum temperature or humidity m...

Страница 47: ...r value is jittering around a sensor limit The following example shows the behavior for a temperature sensor and a hysteresis value of 1 An upper limit of 50 C is set Example 49 9 C is below the upper...

Страница 48: ...ow max Port A2 Off below min Action matrix during operation when limit values are exceeded for given example to above max to below max to above min to below min from above max A1 On A1 On A1 On A2 Off...

Страница 49: ...s of the E Mail server In the normal case this should be the same as the default that is determined by the setting SMTP Connection Security SMTP Connection Security Transmission via SSL or no encrypti...

Страница 50: ...sables the front buttons activates the key lock with the exception of the bootloader activation Allow switching all ports Allows to switch all ports on or off with the front panel buttons Display X de...

Страница 51: ...Specifications...

Страница 52: ...tting and locked yourself out please activate the Bootloader Mode and use GBL_Conf exe to deactivate the IP ACL Alternatively you can reset the device to factory default 4 2 IPv6 IPv6 Addresses IPv6 a...

Страница 53: ...admin rights are assigned for the login otherwise only user access Service Type This is an alternative to Filter Id A service type of 6 or 7 means ad min rights for the HTTP login otherwise only limi...

Страница 54: ...MP software The device supports SNMP protocols v1 v2c and v3 If traps are enabled in the configura tion the device messages are sent as notifications traps SNMP Informs are not sup ported SNMP Request...

Страница 55: ...also used in the 3DES configuration draft reeder snmpv3 usm 3desede 00 If one is not an SNMP expert it is recom mended to try in each case the settings with and without 3DESKey Passwords The password...

Страница 56: ...NET SNMP NET SNMP provides a very widespread collection of SNMP command line tools snm pget snmpset snmpwalk etc NET SNMP is among others available for Linux and Windows After installing NET SNMP you...

Страница 57: ...7 1 5 1 1 0 Unsigned32 RO Number of suppported Power Channels epc8021PowerIndex 77 1 5 1 2 1 1 x Integer32 RO Index of Power Channel entries epc8021ChanStatus 77 1 5 1 2 1 2 x Integer32 RO 0 data not...

Страница 58: ...ltage on CPU Board epc8021CPUSensorVmain 77 1 5 14 3 0 Gauge32 RO Main Voltage on CPU Board epc8021CPUSensorTcpu 77 1 5 14 4 0 Integer32 RO Temperature on CPU Board epc8021NTPTimeValid 77 1 5 15 1 0 I...

Страница 59: ...el entries epc8025ChanStatus 79 1 5 1 2 1 2 x Integer32 RO 0 data not active 1 data valid epc8025AbsEnergyActive 79 1 5 1 2 1 3 x Gauge32 RO Absolute Active Energy counter epc8025PowerActive 79 1 5 1...

Страница 60: ...5 5 2 1 4 x Integer32 RO Active Power epc8025spCurrent 79 1 5 5 2 1 5 x Gauge32 RO Actual Curent on Power Channel epc8025spVoltage 79 1 5 5 2 1 6 x Gauge32 RO Actual Voltage on Power Channel epc8025s...

Страница 61: ...emp DewPoint epc8025ExtSensorName 79 1 6 1 1 32 x OCTETS RW A textual string containing name of a external Sensor 4 6 SSL TLS Standard The device is compatible with TLS v1 1 to TLS v1 3 standards but...

Страница 62: ...recognized by the fact that the generated key file starts with BEGIN RSA PRIVATE KEY If the file starts with BEGIN PRIVATE KEY the file is in PKCS 8 format and the key is not re cognized If you have o...

Страница 63: ...e several command levels The following commands are usable from each level back go back one level help all commands of the actual level help all show all commands logout logout only when login require...

Страница 64: ...ect the output ERR is given at the beginning of the line followed by a description of the fault Successful instructions without special return value will be acknowledged by OK All other return values...

Страница 65: ...is activated but not in the used Telnet client the IAC commands sent at the beginning can appear as interfering characters in the command line partially invisible Editing The following edit functions...

Страница 66: ...0W 2 225V 3 0A 12 996199s P 12 L Power Port 0 13000Wh 1 0W 2 225V 3 0A 12 998218s This command outputs all port sensor values in one line A list of all fields according to the energy sensor table is...

Страница 67: ...or value threshold on this channel The generated mes sage always starts with a and ends with a CR LF This also applies to sensor limit value messages if Console is selected as message channel in Senso...

Страница 68: ...RADIUS login enabled console telnet login delay set OFF 0 ON 1 enables delay after 3 login fails on off console telnet login delay show shows if login delay enabled console telnet pushmsgs config set...

Страница 69: ...email authentication email user set username sets SMTP username email user show shows SMTP username email passwd set passwd sets SMTP password email passwd hash set passwd sets crypted SMTP password...

Страница 70: ...s http port http port show shows http port http portssl set ip_port sets https port http portssl show shows https port http tls mode set TLS12 0 TLS13_12 1 TLS13 2 TLS13_12_11 3 restricts TLS mode htt...

Страница 71: ...1 enables events on off linesensor line_num energy_sensor events show shows if events are enabled linesensor line_num energy_sensor events type set EVT_SYSLOG 0 EVT_SNMP 1 EVT_EMAIL 2 EVT_SMS 3 EVT_G...

Страница 72: ...rt port_num state set OFF 0 ON 1 sets port to new state port port_num state show shows port state port all state set port_list OFF 0 ON 1 sets several ports in one cmd e g port all state set 1 3 5 1 p...

Страница 73: ...d group snmp snmp port set ip_port sets SNMP UDP port snmp port show shows SNMP UDP port snmp snmpget enabled set OFF 0 ON 1 enables SNMP GET cmds on off snmp snmpget enabled show show if SNMP GET cmd...

Страница 74: ...mer rule_num enabled set OFF 0 ON 1 enables rule timer rule_num enabled show shows if rule is enabled timer rule_num name set name sets name of rule timer rule_num name show shows name of rule timer r...

Страница 75: ...since last Energy Counter Reset s 13 Reverse Active Energy Wh 14 Reverse Reactive Energy VARh 15 Reverse Active Energy Resettable Wh 16 Reverse Reactive Energy Resettable VARh 17 Absolute Active Ener...

Страница 76: ...console telnet login show shows if login enabled console telnet login local set OFF 0 ON 1 enables local login on off console telnet login local show shows if local login enabled console telnet login...

Страница 77: ...ow shows email recipient address email server set dns_name sets email SMTP server address email server show shows email SMTP server address email port set ip_port sets email SMTP port email port show...

Страница 78: ...riod show shows sensor Min Max measurement period extsensor beeper set OFF 0 ON 1 enables beeper sensor alarms extsensor beeper show shows if beeper sensor alarms are enabled http enters cmd group htt...

Страница 79: ...st of one line sensor 5 linesensor line_num energy_sensor value showshows energy sensor of given line 5 linesensor line_num ovp show show state of Overvoltage Protection linesensor line_num counter re...

Страница 80: ...IN 0 ABOVEMIN 1 ABOVEMAX 2 BELOWMAX 3 state show LEGACY shows Port state for Power Port Switching actions L linesensor beeper set OFF 0 ON 1 enables beeper for line meter alarms linesensor beeper show...

Страница 81: ...MP 1 EVT_EMAIL 2 EVT_SMS 3 EVT_GSMEMAIL 4 EVT_BEEPER 5 EVT_DISPLAY 6 EVT_CONSOLE 7 enables different event types portsensor port_num energy_sensor events type show shows what event types are enabled p...

Страница 82: ...1 auth timeout set num_secs sets server request timeout radius PRIMARY 0 SECONDARY 1 auth timeout show shows server request timeout radius PRIMARY 0 SECONDARY 1 retries set num sets server number of r...

Страница 83: ...ttons when not enabled system panel enabled show shows if panel buttons are enabled system panel port all set OFF 0 ON 1 enable siwtch all relays from panel buttons system panel port all show shows if...

Страница 84: ...energy_sensor Index Description Unit 0 Forward Active Energy Wh 1 Power Active W 2 Voltage V 3 Current A 4 Frequency 0 01 hz 5 Power Factor 0 001 6 Power Angle 0 1 degree 7 Power Apparent VA 8 Power...

Страница 85: ...ctions the serial terminal must support VT100 emu lation and echo must not be activated In the device configuration on the other hand Activate echo should be set to yes and Raw mode to no Start your t...

Страница 86: ...l Sensors 0x100 0x1ff Input Registers Fan Level 0x200 0x20f Input Registers Line Energy Sensors 0x400 0x39ff Input Registers Port Energy Sensors 0x3a00 0x81ff Input Registers Bank Energy Sensors 0x820...

Страница 87: ...e Error Status Power Sources Offset EPC 8221 8226 0 Bank A 1 Bank B ENC 2111 2191 0 Pwr1 1 Pwr2 ESB 7213 7214 0 Pwr1 1 Pwr2 only 7214 Input Registers Device Resource Start End Function Info Bereich 0x...

Страница 88: ...the address is the port numbers start at zero 0x100 Port 8 Offset In the Expert Sensor Box 7213 7214 the internal sensor corresponds to the value Port 0 and is coded Port 1 for Sensor 2 and Port 2 fo...

Страница 89: ...e Energy Resettable Wh 16 Forward Reactive Energy Resettable VARh 17 Reverse Active Energy Wh 18 Reverse Reactive Energy VARh 19 Reverse Active Energy Resettable Wh 20 Reverse Reactive Energy Resettab...

Страница 90: ...Type 1 Byte 0x0e Read Dev ID code 1 Byte 0x01 Object Id 1 Byte 0x00 Response Code 1 Byte 0x2b MEI Type 1 Byte 0x0e Read Dev ID code 1 Byte 0x01 Conformity Level 1 Byte 0x01 More Follows 1 Byte 0x00 Ne...

Страница 91: ...the max min values of attached sensors State change of digital sensor input ports Exceeding of max min values of the measured power consumption Condition change of overvoltage protection Syslog messag...

Страница 92: ...Support...

Страница 93: ...ryption in SNMPv3 Disable SNMP v2 access Enable STARTTLS or SSL in the e mail configuration Archive configuration files securely In the IP ACL enter only the devices that require access to HTTP or SNM...

Страница 94: ...ader mode and search for it with GBL_Conf exe Then check the TCP IP parameters and change them if neces sary If the device is not found by GBL_Conf exe in bootloader mode you can reset the settings to...

Страница 95: ...rol 8021 8025 2021 GUDE Systems GmbH Support 6 Disable switching events You can set the sending of syslog emails etc when switching ports only concerns Gude devices with relays under System in the sen...

Страница 96: ...l Measurement 10 E Mail 49 Ethernet connnector 7 F Factory Reset 17 FAQ 94 Feature Matrix 6 Firmware Upload 17 Firmware Update 19 G GBL_Conf exe 17 H HTTP 30 HTTPS 30 I Installation 7 IP ACL 29 52 IP...

Страница 97: ...97 Expert Power Control 8021 8025 2021 GUDE Systems GmbH Index Status LED 15 syslog 34 T Technical Specifications 10 Timer 39 Timer Configuration 39 TLS 61 W Watchdog 26...

Страница 98: ...98 Expert Power Control 8021 8025 2021 GUDE Systems GmbH Expert Power Control 8021 8025 2021 GUDE Systems GmbH 3 3 2021...