Fit an outlet tube to the return connection of the heating system to be
flushed, guide this to the drain and fix in place or use a flushing water
calming tank (see accessories).
Install the system divider on the water inlet of the flushing compressor
as per Fig. D-7 or D-8 and connect to a drinking water withdrawal
point using a connection tube.
Check the inlet water pressure and, if necessary, set to a value
permissible for the heating system using an on-site pressure regulator.
A shut-off fitting should be fitted to the inlet flow connection. Close
this fitting to prevent heating water flowing back in the connection
tube of the flushing compressor.
Connect the water outlet of the flushing compressor with a
connection tube on the shut-off fitting (inlet flow connection).
3 | Rinsing of floor heating systems with water and a mixture of water and
air
Attention!
The flushing tube to the drain must be secured during
flushing as the water flows out in a pressurised and pulsating manner.
Slowly open the on-site drinking water withdrawal point on the
flushing compressor's water inlet.
To flush with water, slowly open the shut-off fitting on the inlet flow
connection and monitor the flushing process.
To flush with a mixture of water and gas, insert the power plug of the
flushing compressor and press the program button "Flush with water
+ air" on the flushing compressor control unit.
The flushing effect can be enhanced by also activating the
"Continuous blast air" function.
Monitor the progress of flushing on the outlet tube and on the flow
display on the flushing compressor control unit. The duration of
flushing depends on the degree of soiling.
Flushing of the heating system is normally concluded when particles
are no longer flushed out of the outlet tube and clear water emerges.
Close the drinking water withdrawal point and then close the shut-off
fitting on the inlet flow connection.