5 | Application limits
Flushing of drinking water installations prior to commissioning with a
mixture of water and air as per DIN EN 806-4 and DVGW work sheet
W 557 with a recommended minimum flow speed of 0.5 m/s.
up to DN 50 use of a flushing compressor
with DN 65 and 80 parallel connection* of two flushing compressors,
with DN 80 parallel connection* of up to three flushing compressors
is possible.
Sanitation of corroded or silted up pipe lines with a mixture of water
and air with a recommended minimum flow speed of 1.5 m/s.
up to DN 32 use of a flushing compressor
with DN 40 and 50 parallel connection of two flushing compressors.
*parallel connection is possible with accessories.