GENO
®
-flushing compressor 1988 K
Order no. 015 151 963-inter Created: KONS-gmei-mrie G:\BA-151963-INTER_GENO-SPUELKOMP-1988_K.DOC
46
7.
The volumetric flow is shown on the control unit of the flushing
compressor. If the recommended minimum volumetric flow as per
the table in chapter D 4 point 9 is not reached, this can be
optimised by taking suitable measures, e.g., integration of a
pressure booster (also see chapter D 4).
8.
Th duration of flushing is based on the length of the flushing section
and should amount to a minimum of 15 seconds for each metre.
The duration of flushing of each withdrawal point should be at least
2 minutes. Flushing can be concluded one particles are no longer
flushed out of the withdrawal points and clear water emerges.
9.
Once the necessary flushing parameters have been achieved, the
withdrawal points are closed again in reverse order.
10.
Close the water inlet again and depressurise the installation.
11.
Flushing is documented in the flushing log. By way of additional
documentation, in particular with sanitation flushing, photos of the
dirt which has been flushed out are also recommended in order to
demonstrate the success and necessity of flushing to the customer.
12.
Disassemble the flushing compressor and flushing fittings and
reinstall the installation.
13.
If proof of the perfect condition of the water is required, arrange a
water inspection.
14.
Commission the installation and hand over to the operator.