CHIMNEY INSTALLATION
© 2013 Greenwood Clean Energy, Inc All Rights Reserved V1.9
Page 19
Note: If it is necessary
to use an
exterior
chimney, the chimney
flue size area must not
exceed two times the
minimum flue area for
the furnace. If an
internal
chimney is
used, the chimney flue
size area must not
exceed three times the
minimum flue area for
the furnace.
Connector Flue Pipe
The connection between the Frontier Series flue adapter and the chimney must be 24-gauge stovepipe or
thicker. Maintain a clearance of at least 18 in (45.7 cm) between the connector and combustible surfaces as
shown on the following illustration.
Minimum Installation Clearances (Side View)
Observe the following rules when installing the connector stove pipe.
1.
Where possible, use only corrugated (non-adjustable) elbows. Use 90-degree elbows only as required
and never more than two (they reduce the draft of the chimney).
2.
Make sure all horizontal runs of connector pipe have a minimum outward rise of 1/4” (0.6 cm) per
horizontal 12” (30.5 cm).
3.
If the connector stovepipe must go through a combustible wall before entering the masonry chimney,
consult a qualified mason or chimney dealer. The installation must conform to local building and
fire codes and latest edition of NFPA 211.
4.
Insert the crimped end of the stovepipe inside the outlet collar of the Frontier series flue adapter.
Install additional pipe and elbows with the crimped end towards the furnace.
5.
Seal the connector pipe to the chimney with furnace cement.
6.
Securely support the connector pipe and fasten joints with a minimum of three sheet metal screws or
rivets per joint.
7.
In all cases, follow the chimney manufacturer’s instructions for installation.
Installation of the Connector Pipe into an Existing Chimney
When attaching the connector pipe to the chimney, do not push it
into the chimney (it may plug the chimney and impede the draft).
The following illustration shows proper installation.
Chimney
Greenwood Frontier CX
Side View
Minimum
18”
(46 cm)
Minimum
36”
(92 cm)
Minimum
36”
(92 cm)
Recommended Configuration:
When exhausting through an
existing brick chimney.
Содержание Frontier CX
Страница 1: ......
Страница 3: ...This page intentionally left blank...
Страница 4: ......
Страница 8: ...SAFETY Page 4 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 SAFETY WARNINGS LABEL...
Страница 9: ...SAFETY 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 5 LABEL LOCATIONS...
Страница 10: ...SAFETY Page 6 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 This page intentionally left blank...
Страница 29: ...PLUMBING INSTALLATION 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 25 Pi ping Schematics...
Страница 30: ...PLUMBING INSTALLATION Page 26 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9...
Страница 35: ...WIRING 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 31...
Страница 54: ...WA This page intentionally left blank...
Страница 56: ...This page intentionally left blank...
Страница 57: ...This page intentionally left blank...