WIRING
Page 34
© 2013 Greenwood Clean Energy, Inc All Rights Reserved V1.9
Auxiliary Wiring for Heat from a Backup Furnace or Boiler
Most operators want their existing central furnace or boiler to fire whenever there is insufficient output from
the Greenwood Frontier (i.e., the fire dies down and no one is available to stoke it). This automatic switching
between systems can be enabled by use of an additional aquastat and relay (note: these components are not
included with the furnace).
The aquastat and relay keep the central furnace from firing unless there is insufficient heat coming from the
Frontier Series. A strap-on aquastat, set to 100º F (38°C), breaks the link between the house thermostat and
the central furnace. When the temperature drops below 100º F (38°C), the aquastat re-establishes the link,
allowing the central furnace to fire.
There are also other solutions for your backup heat. Consult your installer for the best solution for your
heating requirements.
Содержание Frontier CX
Страница 1: ......
Страница 3: ...This page intentionally left blank...
Страница 4: ......
Страница 8: ...SAFETY Page 4 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 SAFETY WARNINGS LABEL...
Страница 9: ...SAFETY 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 5 LABEL LOCATIONS...
Страница 10: ...SAFETY Page 6 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 This page intentionally left blank...
Страница 29: ...PLUMBING INSTALLATION 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 25 Pi ping Schematics...
Страница 30: ...PLUMBING INSTALLATION Page 26 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9...
Страница 35: ...WIRING 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 31...
Страница 54: ...WA This page intentionally left blank...
Страница 56: ...This page intentionally left blank...
Страница 57: ...This page intentionally left blank...