Service Manual
8.6 Installation of Outdoor Unit
1. F ix th e S u p p o rt o f O u td o o r U n it(S e le c t it a c c o rd in g to
th e a ctu a l in s ta lla tio n s itu a tio n )
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with
expansion screws.
A Note:
(1) Take su ffic ie n t p ro te ctive m easures w hen insta llin g the
outdoor unit.
(2) Make sure the support can withstand at least four tim es the
unit weight.
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18)
(4) F or th e unit w ith cooling ca p a city o f 2300W ~5000W , 6
expansion screws are needed; for the unit with cooling capacity
o f 6000W ~8000W , 8 expansion screw s are needed; fo r the
unit with cooling capacity of 10000W -16000W , 10 expansion
screws are needed.
Drain vent
b
Chassis
At least 3cm above the floor
Fig.18
Drain hose^j
Outdoor drain joirt
Fig.19
2. In s ta ll D rain J o in t(O n ly fo r c o o lin g and h e a tin g unit)
(1) Connect the outdoor drain jo in t into the hole on the chassis.
(2) Connect the drain hose into the drain vent.
(As show in Fig.19)
3. F ix O u td o o r U nit
(1) Place the outdoor unit on the support.
(2) Fix the foot holes of o utdoor unit w ith bolts. (As show in
Fig.20)
Foot holes
Foot holes
Fig.20
Handle
Fig.21
Valve cover
4. C o n n e c t In d o o r and O u td o o r P ipes
(1) Remove the screw on the handle and valve cover of outdoor
unit and then remove the handle and valve cover.(As show in
Fig.21)
(2) Remove the screw cap of valve and aim the pipe jo in t at the
bellmouth of pipe.(As show in Fig.22)
L iq u id p ip e
g a s p ipe
g a s v a lv e
Fig.22
P ip e jo in t
U n io n nut
(3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
Refer to the following table for wrench moment of force :
Hex nut diameter(mm)
Tightening to rq u e (N m )
0 6
15~20
0 9 .5 2
30~40
0 1 2
45~55
0 1 6
60~65
0 1 9
70~75
5. C o n n e c t O u td o o r E le c tric W ire
(1) Remove the w ire clip; connect the power connection wire
and signal control wire (only for cooling and heating unit) to the
wiring terminal according to the color; fix them with screws.(As
show in Fig.23)
Handle
Fig.23
yellow-
green
N(1)
blue black brown
L
brown
(black)
N
©
blue
yellow-
green
L
N
©
In d o o r u n it c o n n e c tio n
P O W E R
Note: the wiring connect is for reference only,
please refer to the actual one.
(2) Fix the power connection wire and signal control wire with
wire clip.
A N ote:
(1) A fte r tightening the screw, pull the pow er cord slightly to
check if it is firm.
(2) Never cut the power connection wire to prolong or shorten
the distance.
6. Neaten th e Pipes
(1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. sem idiam eter of bending the pipe is
10cm.
(2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room.(As show in
Fig.24)
The drain hos
X
can't raise
upwards
Fig.24
U-shaped curve
Drain hose
Fig.25
60
£
Installation and Maintenance
Содержание GWH18YE-S6DBA2A/I
Страница 10: ...Service Manual Technical Information 7 ...
Страница 24: ...Service Manual Technical Information 21 ...
Страница 58: ...Service Manual 8 Installation 8 1 Installation Dimension Diagram Installation and Maintenance 55 ...
Страница 76: ...Service Manual 5 C om m unica tion M alfunction E6 Installation and Maintenance 73 ...
Страница 77: ...Service Manual 6 M a lfu nction o f d e tecting plate W IFI JF Installation and Maintenance ...
Страница 83: ...Service Manual 80 Installation and Maintenance ...