Service Manual
c.For heating and cooling unit, when 22°C(71.6°F)<Tindoor am bient<26°C(78.8°F) (for cooling only unit, 22°C(71.6°F)<Tindoor
ambient<26°C)(78.8°F), it will keep the original running mode. If the unit is energized for the first time, it will run in fan mode.
© Protection
a. In cooling operation, protection is the same as that under the cooling mode;
b. In heating operation, protection is the same as that under the heating mode;
c. W hen ambient tem perature changes, operation mode will be converted preferentially. Once started, the com pressor willremain
unchanged for at least 6 minutes.
(7)Common Protection Functions and Fault Display under COOL, HEAT, DRY and AUTO Modes
© Overload protection
Ttube: measured tem perature of outdoor heat exchanger under cooling mode; and measured tem perature of indoor heat exchanger under
heating mode.
1) Cooling overload
a .If T tube<52°C(125.6°F), the unit will return to its original operation state.
b.If T tube>55°C(131°F), frequency rise is not allowed.
c.If T tube>58°C(136.4°F), the com pressor will run at reduced frequency.
d .If T tube>62°C(143.6°F), the com pressor will stop and the indoor fan will run at preset speed.
2) Heating overload
a.If T tube<50°C(122°F), the unit will return to its original operation state.
b.If T tube>53°C(127.4°F), frequency rise is not allowed.
c.If T tube>56°C(132.8°F), the com pressor will run at reduced frequency.
d .If T tube>60°C(140°F), the com pressor will stop and the indoor fan will blow residue heat and then stop.
© Exhaust tem perature protection of compressor
If exhaust tem perature>98°C(208.4°F), frequency is not allowed to rise.
If exhaust tem perature>103°C(217.4°F), the com pressor will run at reduced frequency.
If exhaust temperature>110°C(230°F),, the com pressor will stop.
If exhaust tem perature<90°C(194°F), and the com pressor has stayed at stop for at least 3 minutes, the com pressor will resume its operation.
© Communication fault
If the unit fails to receive correct signals for durative 3 minutes, communication fault can be justified and the whole system will stop.
© Module protection
Under module protection mode, the com pressor will stop. W hen the com pressor remains at stop for at least 3 minutes, the com pressor will
resume its operation. If module protection occurs six tim es in succession, the com pressor will not be started again.
© Overload protection
If tem perature sensed by the overload sensor is over 115 , the com pressor will stop and the outdoor fan will stop with a time lag of 30
seconds. If tem perature is below 95 , the overload protection will be relieved.
© DC bus voltage protection
If voltage on the DC bus is below 150V or over 420V, the com pressor will stop and the outdoor fan will stop with a time lag of 30 seconds.
W hen voltage on the DC bus returns to its normal value and the com pressor has stayed at stop for at least 3 minutes, the com pressor will
resume its operation.
© Faults of tem perature sensors
Designation of sensors
Faults
Indoor ambient tem perature
The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Indoor tube tem perature
The sensor is detected to be open-circuited or short-circuited for successive 5 seconds
Outdoor ambient tem perature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds
Outdoor tube tem perature
The sensor is detected to be open-circuited or short-circuited for successive 30 seconds, and no
detection is performed within 10 minutes after defrost begins.
Exhaust
A fter the com pressor has operated for 3 minutes, the sensor is detected to be open-circuited or
short-circuited for successive 30 seconds.
Overload
A fter the com pressor has operated for 3 minutes, the sensor is detected to be open-circuited or
short-circuited for successive 30 seconds.
3. O ther Controls
(1) ON/OFF
Press the remote button ON/OFF: the on-off state will be changed once each time you press the button.
(2) Mode Selection:
Press the remote button MODE, then select and show in the following ways: AUTO, COOL, DRY, FAN, HEAT, AUTO.
(3) Temperature Setting Option Button
Each time you press the remote button TEMP+ or TEMP-, the setting tem perature will be up or down by 1°C(1.8°F). Regulating Range:
16(60.8°F)~30°C(86°F), the button is useless under the AUTO mode.
(4) Time Switch
You should start and stop the machine according to the setting time by remote control.
(5) SLEEP State Control
48
£
Installation and Maintenance
Содержание GWH18YE-S6DBA2A/I
Страница 10: ...Service Manual Technical Information 7 ...
Страница 24: ...Service Manual Technical Information 21 ...
Страница 58: ...Service Manual 8 Installation 8 1 Installation Dimension Diagram Installation and Maintenance 55 ...
Страница 76: ...Service Manual 5 C om m unica tion M alfunction E6 Installation and Maintenance 73 ...
Страница 77: ...Service Manual 6 M a lfu nction o f d e tecting plate W IFI JF Installation and Maintenance ...
Страница 83: ...Service Manual 80 Installation and Maintenance ...