14 of 20
Quick Setup
TERMINAL UNIT
(HEAT EMITTER)
Underfl oor Heating
Screeded (1)
Underfl oor Heating
Plated (2)
Fan Heater
(3)
Fin-Tube
Convector (4)
Radiator
(5)
Baseboard
(6)
MIX DSGN
45°C
55°C
85°C
80°C
80°C
65°C
MIX MAX
55°C
65°C
100°C
90°C
85°C
80°C
MIX MIN
OFF
OFF
40°C
OFF
OFF
OFF
BOILER SENSOR (RETURN / SUPPLY)
The Boiler Sensor DIP switch selects the installation location for the boiler sensor. When the boiler sensor is installed on the
supply side of the boiler loop, the DIP switch must be set to
Supply
. The boiler thermostat should be set at least 11°C higher
than the required design boiler water temperature. The boiler is controlled as described in section C.
For systems where the GEO 360 provides a heat demand to an external boiler control, the boiler sensor should be installed
on the return side of the boiler loop. When the boiler sensor is installed on the return side of the boiler loop, the DIP switch
must be set to Return. The GEO 360 enables the boiler when the position of the mixing valve exceeds the boiler enable DIP
switch setting. The Boiler contact is controlled as described in section C. The boiler’s operating temperature is controlled by its
thermostat, or an external boiler reset control.
The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the
Advanced
/
Installer
DIP switch to
Installer.
OUTDOOR RESET
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
Item,
and buttons. The display will
now show the word ADJUST in the top right corner.
The ROOM OCC adjustment is the first item displayed. Use the or button to set the ROOM
temperature. The ROOM OCC setting is set to the desired room air temperature during the occupied
(Day) mode.
Note:
To increase or decrease space temperature during the occupied (Day) mode, only adjust the
ROOM OCC setting.
Press and release the
Item
button to advance to the ROOM UNOCC adjustment. Use the or
button to set the desired temperature. The ROOM UNOCC setting is set to the desired room air
temperature during the unoccupied (Night) mode.
Note:
To increase or decrease space temperature during the unoccupied (Night) mode, only adjust
the ROOM UNOCC setting.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Use the or
button to set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest
temperature of the year.
Press and release the
Item
button to advance to the
terminal unit (heat emitter)
adjustment. Use
the
or
button to select the desired terminal unit (heat emitter). The terminal unit (heat emitter)
number corresponds to the type of terminal that is being used. The table below lists the terminal
units (heat emitters) and their default values.
Press and release the
Item
button to advance to the units adjustment. Use the or button to
set the scale to °C or °F.
To exit the ADJUST menu, press and release the
Item
button to advance to the ESC item. Then
either press the or button, or leave the buttons alone for 20 seconds.